C7000 Advanced<br />

A3<br />

Control<br />

The graphics A-C show for a DX2-<br />

unit how you obtain a double proportional<br />

control range by approaching<br />

the stop point of the 2nd compressor<br />

to the start point of the suction<br />

valve.<br />

Valves<br />

Suction valve<br />

The start temperature for the suction valve<br />

is entered as a positive difference to the<br />

room temperature setpoint. ➊<br />

You can adjust a gradient, which determines<br />

the temperature range in which<br />

the valve opening increases from 0 to<br />

100%.➋<br />

If the A/C unit is equipped with two refrigerant<br />

circuits, only the first refrigerant circuit<br />

can be equipped with a suction valve.<br />

Depending on how you choose the start<br />

points for the compressors you can exploit<br />

the proportional control range of the suction<br />

valve to a maximum.(see examples)<br />

The suction valve has a control range of<br />

50% - 100% of the compressor cooling<br />

capacity.<br />

C7000 PT2<br />

➊<br />

➋<br />

b3<br />

./Suction val 1 □ 27<br />

→Start 0,0 K<br />

+Gradient 0,5 K<br />

On 0,0 %<br />

The surrounded numbers refer to the corresponding<br />

passages in the descriptive text.<br />

The operation status/opening degree of the<br />

suction valve is displayed in the last line.<br />

Graphic A Graphic B Graphic C<br />

Suction<br />

Suction<br />

valve<br />

valve<br />

Suction<br />

valve<br />

Comp. 1 Comp. 2<br />

Comp. 1 Comp. 2<br />

Comp. 1 Comp. 2<br />

Cool.<br />

cap.<br />

200%<br />

Setpoint<br />

Cool.<br />

cap.<br />

200%<br />

Setpoint<br />

Cool.<br />

cap.<br />

200%<br />

Setpoint<br />

100%<br />

75%<br />

50%<br />

Comp. 2<br />

Comp. 1<br />

175%<br />

100%<br />

75%<br />

50%<br />

Comp. 2<br />

Comp. 1<br />

150%<br />

100%<br />

75%<br />

50%<br />

Comp. 2<br />

Comp. 1<br />

➊<br />

➋<br />

➊<br />

➋<br />

➊<br />

➋<br />

C7000<br />

The corresponding commands:<br />

➊<br />

➋<br />

suctionv 1 start 0,2<br />

suctionv 1 grad 0,9<br />

Times are entered in seconds.<br />

The surrounded numbers refer to the corresponding<br />

passages in the descriptive text.<br />

E/1006/57/47