AIR CONDITIONING
AIR CONDITIONING
AIR CONDITIONING
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
C7000 Advanced<br />
A3<br />
Control<br />
The graphics A-C show for a DX2-<br />
unit how you obtain a double proportional<br />
control range by approaching<br />
the stop point of the 2nd compressor<br />
to the start point of the suction<br />
valve.<br />
Valves<br />
Suction valve<br />
The start temperature for the suction valve<br />
is entered as a positive difference to the<br />
room temperature setpoint. ➊<br />
You can adjust a gradient, which determines<br />
the temperature range in which<br />
the valve opening increases from 0 to<br />
100%.➋<br />
If the A/C unit is equipped with two refrigerant<br />
circuits, only the first refrigerant circuit<br />
can be equipped with a suction valve.<br />
Depending on how you choose the start<br />
points for the compressors you can exploit<br />
the proportional control range of the suction<br />
valve to a maximum.(see examples)<br />
The suction valve has a control range of<br />
50% - 100% of the compressor cooling<br />
capacity.<br />
C7000 PT2<br />
➊<br />
➋<br />
b3<br />
./Suction val 1 □ 27<br />
→Start 0,0 K<br />
+Gradient 0,5 K<br />
On 0,0 %<br />
The surrounded numbers refer to the corresponding<br />
passages in the descriptive text.<br />
The operation status/opening degree of the<br />
suction valve is displayed in the last line.<br />
Graphic A Graphic B Graphic C<br />
Suction<br />
Suction<br />
valve<br />
valve<br />
Suction<br />
valve<br />
Comp. 1 Comp. 2<br />
Comp. 1 Comp. 2<br />
Comp. 1 Comp. 2<br />
Cool.<br />
cap.<br />
200%<br />
Setpoint<br />
Cool.<br />
cap.<br />
200%<br />
Setpoint<br />
Cool.<br />
cap.<br />
200%<br />
Setpoint<br />
100%<br />
75%<br />
50%<br />
Comp. 2<br />
Comp. 1<br />
175%<br />
100%<br />
75%<br />
50%<br />
Comp. 2<br />
Comp. 1<br />
150%<br />
100%<br />
75%<br />
50%<br />
Comp. 2<br />
Comp. 1<br />
➊<br />
➋<br />
➊<br />
➋<br />
➊<br />
➋<br />
C7000<br />
The corresponding commands:<br />
➊<br />
➋<br />
suctionv 1 start 0,2<br />
suctionv 1 grad 0,9<br />
Times are entered in seconds.<br />
The surrounded numbers refer to the corresponding<br />
passages in the descriptive text.<br />
E/1006/57/47