6.2.2 Control commands - C7000<br />

A typical control command is structured as follows:<br />

top command<br />

sub-command<br />

drycool 1 startsum 32,0<br />

command component parameter parameter<br />

number designation value<br />

Following a summary of the most frequent sub-commands:<br />

type 1/2/3..<br />

start #,#<br />

startsum #,#<br />

startwin #,#<br />

hys #,#<br />

hyssum #,#<br />

hyswin #,#<br />

press #<br />

grad #,#<br />

pretime #<br />

preopen #<br />

prespeed #<br />

conf 0/1<br />

ain #<br />

din # / alarm #<br />

aout #<br />

dout #<br />

basicalarm 0/1<br />

alarmdelay #<br />

alarmprio #<br />

runtime #<br />

hand 0/1<br />

handon 0/1/#<br />

sets the type of control (mostly 1=2-point control, 2 = proportional)<br />

sets the startpoint (temperature or humidity according to the component)<br />

sets the summer operation startpoint<br />

sets the winter operation startpoint<br />

sets the hysteresis (for on/off-controlled components)<br />

sets the summer operation hysteresis<br />

sets the winter operation hysteresis<br />

sets the pressure startpoint<br />

sets the gradient (for proportionally controlled components)<br />

sets the pre-start time in seconds<br />

sets the pre-opening of a valve in %<br />

sets the pre-speed of a fan or pump in %<br />

0 = deactivates a component from the configuration<br />

1 = activates a component for the configuration<br />

assigns the analogous input # to the component (sensor)<br />

assigns the digital input # to the component related alarm<br />

assigns the component to the analogous output #<br />

assigns the component to the digital output #<br />

0 = no common alarm when component alarm<br />

1 = common alarm when component alarm<br />

sets the alarmdelay in seconds<br />

assigns the alarm to alarm relay #<br />

sets the runtime in hours<br />

0 = disables manual operation, 1 = enables manual operation<br />

0/1/# = switches off/on the component in manual operation or sets a value in % for proportionally<br />

controlled components<br />

E/1006/57/39