C7000 Advanced<br />
Info<br />
C7000 PT2<br />
Info □ 27<br />
→Actual<br />
Status<br />
Runtimes<br />
Events<br />
Alarm<br />
Current values<br />
This window shows the actual values of<br />
the connected sensors the same as the<br />
setpoints adjusted at the controller.<br />
Furthermore the setpoints shifted by the<br />
controller (CORR.) are displayed. These<br />
setpoints are due to the week cycle<br />
program (see page 84) or by the sensor<br />
limitation control (see page 81). The shifted<br />
setpoints are priority setpoints.<br />
Here you can see the measured values<br />
for the zone. These values represent an<br />
average value for each parameter, which<br />
is calculated of all sensors of the units<br />
which are assigned to the same zone.<br />
These are the measured values for the<br />
unit.<br />
These are several sensor values of the<br />
unit.<br />
visible window - display size<br />
Info/Actual □ 27<br />
→Temp 24,1 °C<br />
Humidity 45,3 %rh<br />
Set 24,0 °C<br />
Set 45,0 %rh<br />
Set corr 24,2 °C<br />
Set corr 44,7 %rh<br />
Z.room 24,1 °C<br />
Z.room 45,3 %rh<br />
Z.supply 14,5 °C<br />
Z.supply 43,9 %rh<br />
U.room 26,8 °C<br />
U.room 47,8 %rh<br />
U.supply 15,8 °C<br />
U.supply 42,8 %rh<br />
Water 1 7,8 °C<br />
Water 2 9,8 °C<br />
Outside 27,8 °C<br />
Outside 65,3 %rh<br />
Conden 1 19,5 bar<br />
Conden 2 18,5 bar<br />
Conden 1 42,7 °C<br />
Conden 2 35,7 °C<br />
Evap 1 5,5 bar<br />
Evap 2 6,5 bar<br />
Evap 1 8,4 °C<br />
Evap 2 9,4 °C<br />
The complete menu can be scrolled with<br />
the up and down arrow keys.<br />
E/1006/57/35