6. Operation<br />

6.1 Info level<br />

6.1.1 Info commands - C7000<br />

Generally each component- or A/C unit command which is entered without parameters only displays information<br />

without changing adjustments. However, the following commands give a general overview about the unit state and<br />

configuration.<br />

equip - shows the components and its number, also the extension cards (dig/ana)<br />

state - shows the unit- and functional (cooling, heating etc.) runtimes and the unit/component state<br />

is 1 - - setpoints, actual zone/unit values, limit values<br />

is 2 - - alarm delay, priority, common alarm assignment for each limit value alarm<br />

is 3 - - control type, sensor limitation values, cooling priority, winter operation, ups mode, outside temp. for<br />

condensation pressure reduction, gradient for press. reduction, winter start delay, bus/global address,<br />

temperature difference for overload activation, last service, service interval,<br />

- assignment of in/outputs: common alarm, winter operation, remote on/off, ups operation,<br />

actual temp./humidity, CW cooling off<br />

wprg - shows the programmed timer function for the week<br />

events - shows all registered events (maximum 200, alarms & unit on/off)<br />

ups - shows the ups (uninterrupted power supply) configuration<br />

6.1.2 Info overview - C7000 Plus<br />

Info □ 27<br />

→Actual<br />

Status<br />

Runtimes<br />

Events<br />

Alarm<br />

Info/Actual □ 27<br />

→Temp 24,1 °C<br />

Humidity 45,3 %rh<br />

Set 24,0 °C<br />

Set 45,0 %rh<br />

Set corr 24,2 °C<br />

Set corr 44,7 %rh<br />

Z.room 24,1 °C<br />

Z.room 45,3 %rh<br />

Z.supply 14,5 °C<br />

Z.supply 43,9 %rh<br />

U.room 26,8 °C<br />

U.room 47,8 %rh<br />

U.supply 15,8 °C<br />

U.supply 42,8 %rh<br />

Water 1 7,8 °C<br />

Water 2 9,8 °C<br />

Outside 27,8 °C<br />

Outside 65,3 %rh<br />

Conden 1 19,5 bar<br />

Conden 2 18,5 bar<br />

Conden 1 42,7 °C<br />

Conden 2 35,7 °C<br />

Evap 1 5,5 bar<br />

Evap 2 6,5 bar<br />

Evap 1 8,4 °C<br />

Evap 2 9,4 °C<br />

Info/State □ 27<br />

→Cooling 1<br />

Heating 0<br />

Humidi 0<br />

Dehum 0<br />

Info/Runtimes □ 27<br />

→U.start 180 h<br />

U.stop 120 h<br />

U.cooling 125 h<br />

U.heating 123 h<br />

U.humi 145 h<br />

U.dehumi 260 h<br />

Info/Events □ 27<br />

→13.11 Start<br />

12.11 Unit on<br />

11.11 Unit off<br />

Info/Alarm □ 27<br />

→General<br />

Alarm<br />

Alarm/General □ 27<br />

→Reset 0<br />

Alarm 0<br />

Common 0<br />

Alarm/Alarm □ 27<br />

Comp 1 Al 1<br />