23.10.2014 Views

AIR CONDITIONING

AIR CONDITIONING

AIR CONDITIONING

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2.3.2 Assignment - EAIO<br />

The assignment depends on the unit version (DX1, DX2, CW). Explanation see page 7.<br />

Pin Designation DX1 DX2 CW<br />

1 +Ub/Ib<br />

2 Ain 6<br />

3 GND<br />

4 GND<br />

5 +Ub/Ib<br />

6 Ain 7<br />

7 GND<br />

8 GND<br />

9 +Ub/Ib<br />

10 Ain 8<br />

11 GND<br />

12 GND<br />

13 +Ub/Ib<br />

14 Ain 9<br />

15 GND<br />

16 GND<br />

universal sensor 4<br />

Outside temperature<br />

universal sensor 5<br />

Condensation pressure<br />

universal sensor 6<br />

Evaporation pressure<br />

universal sensor 7<br />

Water temp. (G)<br />

17 Aout 5 Suction valve / compressor1<br />

18 GND<br />

or actual humidity<br />

19 Aout 6<br />

20 GND<br />

21 Aout 7<br />

22 GND<br />

actual temperature<br />

23 Aout 8 EEV (with 0-10V) or<br />

24 GND<br />

proportional dehumidific.<br />

universal sensor 4<br />

Outside temperature<br />

universal sensor 5<br />

Condensation pressure 1<br />

universal sensor 6<br />

Condensation pressure 2<br />

universal sensor 7<br />

Water temp. (G) or evaporation<br />

pressure 1<br />

Suction valve / compressor1<br />

or actual humidity<br />

Suction valve /<br />

compressor 2/ act. temp.<br />

universal sensor 4<br />

Outside temperature<br />

universal sensor 5<br />

Water temp. 2 (CW2)<br />

universal sensor 6<br />

- free -<br />

universal sensor 7<br />

- free -<br />

actual humidity<br />

actual temperature<br />

HWR valve HWR valve HWR-valve<br />

EEV (with 0-10V) or<br />

proportional dehumidific.<br />

proportional<br />

dehumidification<br />

X10 SUB-D 15 Bus 3 I 2 C (plug) Bus 3 I 2 C (plug) Bus 3 I 2 C (plug)<br />

E/1006/57/13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!