C7000 Advanced<br />

A5<br />

Control<br />

Valves<br />

G-valve<br />

The pressure setpoint is entered in the<br />

2nd line and relates to the refrigerant condensation<br />

pressure in the condenser. ➊<br />

The pre-start serves to provide a sufficient<br />

flow for the heat absorbing medium and<br />

to pre-cool the heat absorbing medium.<br />

When compressor operation is requested,<br />

the G-valve opens and the compressor<br />

start is delayed by the pre-start time. ➋<br />

The pre-open value is the G-valve opening<br />

which should be obtained during the prestart<br />

time. ➌<br />

To avoid a constant discrepancy from<br />

the set value there are three parameters,<br />

which imitate the behaviour of an integral<br />

control.<br />

The control factor ➍ is the decisive value,<br />

by which the extent of the control correction<br />

is adjusted in the way of calculating<br />

the actuating variable after the lapse of<br />

an adjustable control cycle ➎ (0-10 sec)<br />

according to the following formula:<br />

S new = S old - f • (set value - actual value)<br />

S: actuating variable - here valve opening<br />

f: control factor<br />

Set value: condensation pressure<br />

To avoid a drastical change you can adjust<br />

a maximum control correction ➏ (0<br />

- ±10%). This control correction relates to<br />

the old actuating variable in each cycle.<br />

C7000 PT2<br />

➊<br />

➋<br />

➌<br />

➍<br />

➎<br />

b5<br />

Cool/G-valve □ 27<br />

→Set 18,0 bar<br />

+Pre-start 5 s<br />

+Pre-open 50 %<br />

+I-factor 10 %<br />

+D-factor 20 %<br />

On 0,0 %<br />

The surrounded numbers refer to the corresponding<br />

passages in the descriptive text.<br />

The operation status of the G-valve is displayed<br />

in the last line.<br />

C7000<br />

The corresponding commands:<br />

➊ gvalve press 18,4<br />

➋ gvalve pretime 15<br />

➌ gvalve preopen 40<br />

➍ gvalve fact 2<br />

➎ gvalve concyc 5<br />

➏ gvalve maxc 5<br />

Times are entered in seconds.<br />

The surrounded numbers refer to the corresponding<br />

passages in the descriptive text.<br />

E/1006/57/49