Appendix A -- Program Directory<br />
unistat control V3.8.1<br />
Appendix A - Program Directory<br />
The setting of operating modes or unit parameters is carried out using programs. These are<br />
stored in an extensive memory in the control panel. Some programs only switch from one<br />
operating mode to an alternative (for example ‘control mode’ program 3), with others<br />
parameters have to be entered (for example ‘set point’ program 0) and some need a proper<br />
dialogue (for example ‘setting heating program’ program 20).<br />
The program selection is initiated by pressing , after that the program number must be<br />
entered, then press . A short description of the program appears on the LCD display<br />
unit together with a display of the current setting.<br />
Entering the numerical values for the parameters, for example the set point, is done via the<br />
number keys … , sometimes also by using the decimal point and the minus<br />
sign . The programming is confirmed by pressing .<br />
Corrections are possible by pressing . A programming mistake is stopped by pressing<br />
. Should a mistake be confirmed with , it can still be rectified by calling up the<br />
program and entering the new parameter.<br />
! Not every control panel is equipped with all programs! This depends on the software<br />
status!<br />
The software of the unistat control monitors logic discrepancies. A change of the minimum –<br />
maximum set point, for example, during activated circulation is not possible. If you try such<br />
change you will be warned (display ‘ Not allowed!’). The programmed change is rejected.<br />
Program 0: Setting set point<br />
After selection, ‘enter set point’ appears on LCD display. The set point is entered with <br />
to , and keys. The actual programming is done by pressing . The<br />
value of the set point is depending on the currently set minimum set point and maximum set<br />
point. The rule is:<br />
Minimal set point < = set point < = maximum set point.<br />
If this rule is not obeyed, an error message appears and the setting is ignored. The step size<br />
for the entry is 0.1K. You can choose to enter the second digit after the comma, by not<br />
pressing at the end, but by just entering another digit. With this you can reach a<br />
setting resolution of 0.01K.<br />
entering set point of 20.5 °C,<br />
(without !) setting a set<br />
point of 20.55°C.<br />
The activation of this program is achieved by pressing , this is the<br />
same as pressing the Hotkey .<br />
Program 1: Setting Of Minimum Set Point<br />
After selection, the program name appears and the current minimum set point appears.<br />
The value is entered by pressing keys … and . Only whole numbers are<br />
possible, no digits after comma. The entering is done by pressing . The value of the<br />
minimum set point is depending on the current set point and the unit parameters<br />
(Lowest permissible temperature). The rule is:<br />
Lowest permissible temperature < = minimum set point < = set point.<br />
If this rule is broken, an error message appears, and the setting is ignored.<br />
19