Voltage 230/400 V(∆Y), 50 Hz<br />

RPM 1470<br />

Current 227/131 Amps<br />

2.6.13 Generator excitation system<br />

The turbo-generator <strong>of</strong> 210 MW unit <strong>of</strong> GPS utilises the quick static self excitation<br />

system with booster trans<strong>for</strong>mer in series controlled by sylicon valves (thyristor)<br />

and strong automatic excitation system.<br />

Stand by excitor<br />

Generator<br />

Motor<br />

Type BT 171-7 KT3 AC3-2-17-61-6T3<br />

Power KW 990/3250 1250<br />

Voltage V 470/840 6600<br />

Current A 2100/3860 147<br />

Speed rpm 990/970 990<br />

2.6.14 Trans<strong>for</strong>mer (<strong>Unit</strong> step up trans<strong>for</strong>mer) & Circuit Breaker<br />

<strong>Unit</strong> no 3 consists <strong>of</strong> 2 <strong>Unit</strong> Step Up trans<strong>for</strong>mers <strong>of</strong> 125 MVA each. Also Air Blast Circuit<br />

Breaker (ABCB) used as Circuit Breaker.<br />

Sl Description Trans<strong>for</strong>mer-1 Trans<strong>for</strong>mer-2<br />

1 Type TDU-125000/230-73TI TDU-125000/230-73TI<br />

2 Rated Capacity 125 MVA 125 MVA<br />

3 Rated Current 314/4600 314/4600<br />

4 Rated Voltage 242±2X2.5%/15.75 KV 242±2X2.5%/15.75 KV<br />

5 Short Circuit Voltage 11.2% 11.2%<br />

6 Vector Group Y/Delta-1 Y/Delta-1<br />

7 Circuit Breaker Air Blast Circuit Breaker Air Blast Circuit Breaker<br />

2.6.15 Protection system<br />

Protection system <strong>of</strong> different equipment are used.<br />

2.6.16 Battery/ DC system<br />

<strong>Unit</strong> consists <strong>of</strong> 230 V DC System.<br />

2.7 Other electrical system<br />

a. One (1) lot <strong>of</strong> 400 V switchgear.<br />

b. Cables and wiring <strong>for</strong> interconnection between the equipment.<br />

2.8 Emergency Diesel Generating Set<br />

One (1) set <strong>of</strong> emergency diesel generating set (capacity 1000 KVA at 0.8 p.f.,<br />

1500 rpm) complete with ancillary equipment having diesel storage capacity <strong>for</strong> 24<br />

hours <strong>of</strong> continuous operation <strong>for</strong> supplying power to essential auxiliaries. EDG<br />

shall be <strong>of</strong> automatic starting system [compressed air/ Battery] including quick start<br />

& loading capability. The starting system shall be capable <strong>of</strong> carrying out at least<br />

five (5) consecutive start without auxiliary power supply. In case <strong>of</strong> power failure in<br />

Re-Powering <strong>Ghorasal</strong> 210 MW 3 rd <strong>Unit</strong> (Vol-2A <strong>of</strong> 2) 20