e kept (without bay equipment) <strong>for</strong> two (02) nos. <strong>of</strong> 230 kV line which<br />

will connect Power Plant Sub Station with <strong>Ghorasal</strong> Grid Sub Station.<br />

2.10.2 Trans<strong>for</strong>mers and Associated Equipment (<strong>for</strong> GT)<br />

1) Two (2) sets <strong>of</strong> three phase step-up trans<strong>for</strong>mers with associated<br />

equipment. Two (2) sets <strong>for</strong> GT(s) and having capacity to match the power<br />

output <strong>of</strong> GTG(s) with the following features:<br />

• Type : Oil immersed Three phase, outdoor power<br />

trans<strong>for</strong>mer<br />

• Rating : To meet the requirement <strong>of</strong> the specification<br />

as stated above & Clause-8<br />

• Voltage ratio <strong>of</strong> :15.75 (or as per Generation Voltage) / 230 kV<br />

trans<strong>for</strong>mer at full load<br />

• Connection :Ynd 1 as shown in single<br />

line diagram.<br />

: HV winding LV winding<br />

• Rated insulation level 650 kV (Peak) 75 kV (Peak)<br />

• Lighting impulse Withstand : 650 kV (Peak) 75 kV Peak<br />

Voltage (1.2/50 micro sec.)<br />

• Power frequency withstand : 275 kV 28 kV<br />

Voltage (<strong>for</strong> 1 min).<br />

• Impedance voltage : Shall be within the range <strong>of</strong><br />

15% and 18%<br />

• Tap changer : On load at high tension<br />

winding +8 x 1.25% to -12x1.25%.<br />

• Termination :Outdoor bushing <strong>for</strong> Cable Pot<br />

High tension side<br />

Head connection<br />

• Low tension side : Isolated & insulated phase copper<br />

bus duct.<br />

2) One (1) lot <strong>of</strong> associated equipment.<br />

2.10.3 <strong>Unit</strong> Auxiliary Trans<strong>for</strong>mer, Station Trans<strong>for</strong>mers and Associated<br />

Equipment (<strong>for</strong> GT)<br />

1) Two (2) sets <strong>of</strong> unit auxiliary trans<strong>for</strong>mer (2 x 110% <strong>of</strong> total aux. power<br />

requirement but each capacity not less than 25 MVA) and associated<br />

equipment with the following features:<br />

• Type : Oil immerse, three phase and<br />

two windings, outdoor power<br />

trans<strong>for</strong>mer.<br />

• Rating : 25 MVA<br />

• Rated high voltage :15.75 kV (or as per Generation Voltage)<br />

Re-Powering <strong>Ghorasal</strong> 210 MW 3 rd <strong>Unit</strong> (Vol-2A <strong>of</strong> 2) 22