4 Hour<br />

30 minutes Insulation 4 Hour Integrity<br />

Double Skin Firewall with Instaloc 40 Spacer System<br />

& Rockfibre Quilt (vertical outside rail)<br />

This system is intended for use<br />

as an external wall, sited at least<br />

1 metre from a relevant boundary.<br />

It is not suitable for partitions.<br />

Assessment of fire resistance refers<br />

to cladding system which must be<br />

supported at base or by a fire rated<br />

eaves beam. The assessment refers<br />

to non-loadbearing walls. The<br />

cladding system carries no vertical<br />

load other than its own dead weight.<br />

Installation of this system to be<br />

in accordance with approved<br />

document B (Fire Spread) in the<br />

Building Regulations 2000.<br />

Insulation<br />

Two layers of 80mm thick Rockfibre<br />

insulation quilt. 23kg/m 3 nominal density.<br />

Lining Panel<br />

Corus Panels <strong>and</strong> Profiles colorcoated<br />

galvanised steel 0.4/0.7mm thick.<br />

Instaloc 40<br />

160mm bracket is required with 160mm<br />

insulation. For thicker insulation<br />

increase bracket size accordingly.<br />

Outer Cladding<br />

Corus Panels <strong>and</strong> Profiles colorcoated<br />

galvanised steel 0.5/0.7mm thick.<br />

Sheeting Rail<br />

Sheeting rails supplied by others.<br />

The rail is not fire protected so a facility<br />

for expansion is required (slotted fixing<br />

holes).<br />

Construction Notes<br />

All fixings <strong>and</strong> components to be<br />

steel.<br />

All outer sheet side laps must be<br />

stitched at not more than 600mm<br />

centres.<br />

Lining panels do not require stitching.<br />

The Building Regulations 2000<br />

Approved Document L2 – April 2002<br />

Contact Corus Panels <strong>and</strong> Profiles<br />

Technical Department for information on<br />

the insulation thickness needed for this<br />

system to meet part L requirements.<br />

Warrington Fire Research Centre<br />

number 141917.<br />

System assessment to comply with<br />

BS476 part 22.1987 in relation to<br />

internal fire.<br />

Stability = 240 minutes<br />

Integrity = 240 minutes<br />

Insulation = 30 minutes<br />

Firewall Systems 21