4 Hour<br />
15 Minutes Insulation 4 Hour Integrity<br />
Structural Liner Tray<br />
This system is intended for use<br />
as an external wall, sited at least<br />
1 metre from a relevant boundary.<br />
It is not suitable for partitions.<br />
Assessment of fire resistance refers<br />
to cladding system which must be<br />
supported at base or by a fire rated<br />
eaves beam. The assessment refers<br />
to non-loadbearing walls. The<br />
cladding system carries no vertical<br />
load other than its own dead weight.<br />
Installation of this system to be<br />
in accordance with approved<br />
document B (Fire Spread) in the<br />
Building Regulations 2000.<br />
Liner Tray<br />
Corus Panels <strong>and</strong> Profiles HL600/130<br />
Structural Liner Tray.<br />
Thermal Break Strip<br />
Rockfibre fire barrier strip<br />
50mm x 35mm 240kg/m 3 density.<br />
Fastener<br />
5.5mm diameter by 45mm long selfdrilling<br />
fastener e.g. SD3-T15-5.5x45.<br />
Side Stitching<br />
Side stitching in web at tray interlocks<br />
400mm maximum centres.<br />
Insulation<br />
Rockfibre insulation, minimum<br />
160mm thick 23kg/m 3 nominal density.<br />
Outer Cladding<br />
Corus Panels <strong>and</strong> Profiles External<br />
Cladding 0.5mm thick steel.<br />
Warrington Fire Research Centre number<br />
C54353.<br />
System assessment to comply with BS476<br />
part 22.1987 in relation to internal fire.<br />
Stability = 240 minutes<br />
Integrity = 240 minutes<br />
Insulation = 15 minutes<br />
The Building Regulations 2000 Approved<br />
Document L2 – April 2002<br />
The above achieves 0.35 W/m 2 K in<br />
accordance with Approved Document L2<br />
April 2002.<br />
Firewall Systems 23