Pre-mixed condensation gas heating modules<br />
• Cascade connection<br />
- REPLY N is a heating module intended for single or cascade operation. Two or more REPLY modules can be cascade connected (5<br />
heating modules at maximum), as shown in the figure below.<br />
gas Attacco connection Gas<br />
delivery Mandata<br />
return Ritorno<br />
A cascade control room is available on demand, allowing advanced management of the two<br />
shells inside the boiler. Each control room is capable of controlling a maximum of 5<br />
furnaces. As a consequence the number of control rooms being necessary for such<br />
operation changes depending on the number of REPLY N modules connected (see table on<br />
your right).<br />
Reply N modules necessary control rooms<br />
n° n°<br />
2 1<br />
3 2<br />
4 2<br />
5 2<br />
6 3<br />
- -<br />
- -<br />
• Flue<br />
- For cascade connection of more than one module, connect the flue outlet (Ø 150) of each single module as shown in the figure, making<br />
sure that the header and flue diameter values correspond to those reported in the table below.<br />
Warning: The header shall feature a slope towards the<br />
condensation discharge amounting to at least 3°.<br />
Ø<br />
150<br />
3°<br />
Reply N modules<br />
Header/flue<br />
n° Ø mm<br />
1 150<br />
2 200<br />
3 250<br />
4 300<br />
5 350<br />
47