Pre-mixed condensation gas heating modules<br />

• Cascade connection<br />

- REPLY N is a heating module intended for single or cascade operation. Two or more REPLY modules can be cascade connected (5<br />

heating modules at maximum), as shown in the figure below.<br />

gas Attacco connection Gas<br />

delivery Mandata<br />

return Ritorno<br />

A cascade control room is available on demand, allowing advanced management of the two<br />

shells inside the boiler. Each control room is capable of controlling a maximum of 5<br />

furnaces. As a consequence the number of control rooms being necessary for such<br />

operation changes depending on the number of REPLY N modules connected (see table on<br />

your right).<br />

Reply N modules necessary control rooms<br />

n° n°<br />

2 1<br />

3 2<br />

4 2<br />

5 2<br />

6 3<br />

- -<br />

- -<br />

• Flue<br />

- For cascade connection of more than one module, connect the flue outlet (Ø 150) of each single module as shown in the figure, making<br />

sure that the header and flue diameter values correspond to those reported in the table below.<br />

Warning: The header shall feature a slope towards the<br />

condensation discharge amounting to at least 3°.<br />

Ø<br />

150<br />

3°<br />

Reply N modules<br />

Header/flue<br />

n° Ø mm<br />

1 150<br />

2 200<br />

3 250<br />

4 300<br />

5 350<br />

47

Hooray! Your file is uploaded and ready to be published.