r0067 CO: Act. output current limit Min: -<br />

Datatype: Float Unit: A Def: -<br />

P-Group: CONTROL Max: -<br />

Level<br />

3<br />

Displays valid maximum output current of inverter.<br />

P<strong>03</strong>05<br />

Motor<br />

Inverter<br />

P0640<br />

r0209<br />

Motor protection<br />

Inverter protection<br />

Min<br />

r0067<br />

Dependency:<br />

This value is influenced by P0640 (Motor overload factor), the derating characteristics and the thermal<br />

motor and inverter protection.<br />

Note:<br />

P0610 (motor I2t temperature reaction) and P0290 (inverter overload reaction) define reaction when limit is<br />

reached.<br />

Normally :<br />

- current limit (r0067) = rated motor current P<strong>03</strong>05 x motor overload factor P0640.<br />

- It is less than or equal to maximum inverter current r0209.<br />

The current limit may be reduced if the motor or inverter thermal model calculation indicates that<br />

overheating will occur.<br />