21.11.2014 Views

Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens

Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens

Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Parameter</strong>s <strong>04</strong>/<strong>03</strong><br />

P1232 DC braking current Min: 0<br />

CStat: CUT Datatype: U16 Unit: % Def: 100<br />

P-Group: FUNC Active: Immediately QuickComm.: No Max: 250<br />

Level<br />

3<br />

Defines level of DC current in [%] relative to rated motor current (P<strong>03</strong>05).<br />

The DC Brake (DC Injection Brake) can be issued observing the following dependencies:<br />

- OFF1 or OFF3 ==> see P1233<br />

- DIN or USS ==> see below<br />

DIN<br />

P070x = 25<br />

1<br />

0<br />

USS * )<br />

⏐f⏐<br />

Ctrl. wd. 2 Bit09<br />

f*<br />

DC braking<br />

f_set<br />

t<br />

f_act<br />

i<br />

P<strong>03</strong>47<br />

t<br />

DC braking active<br />

t<br />

r0053<br />

Bit 00<br />

1<br />

0<br />

t<br />

Note: DC brake can be applied in drive states r0002 = 1, 4, 5<br />

*) <strong>SINAMICS</strong> <strong>G110</strong> CPM110 USS only<br />

<strong>Parameter</strong> <strong>List</strong> <strong>SINAMICS</strong> <strong>G110</strong><br />

58 6SL3298-0BA11-0BP0

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!