Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Parameter</strong>s <strong>04</strong>/<strong>03</strong><br />
P07<strong>03</strong> Function of digital input 2 Min: 0<br />
CStat: CT Datatype: U16 Unit: - Def: 9<br />
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 29<br />
Selects function of digital input 2.<br />
Possible Settings:<br />
0 Digital input disabled<br />
1 ON/OFF1<br />
2 ON reverse /OFF1<br />
3 OFF2 - coast to standstill<br />
4 OFF3 - quick ramp-down<br />
9 Fault acknowledge<br />
10 JOG right<br />
11 JOG left<br />
12 Reverse<br />
13 MOP up (increase frequency)<br />
14 MOP down (decrease frequency)<br />
15 Fixed frequency (Direct selection)<br />
16 Fixed frequency (Direct selection + ON)<br />
21 Local/remote<br />
25 DC brake enable<br />
29 External trip<br />
Details:<br />
See P0701 (function of digital input 0).<br />
P07<strong>04</strong> Function of digital input 3 Min: 0<br />
CStat: CT Datatype: U16 Unit: - Def: 0<br />
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 29<br />
Level<br />
2<br />
Level<br />
2<br />
Selects function of digital input 3 (via analog input).<br />
Possible Settings:<br />
0 Digital input disabled<br />
1 ON/OFF1<br />
2 ON reverse /OFF1<br />
3 OFF2 - coast to standstill<br />
4 OFF3 - quick ramp-down<br />
9 Fault acknowledge<br />
10 JOG right<br />
11 JOG left<br />
12 Reverse<br />
13 MOP up (increase freq.)<br />
14 MOP down (decrease freq.)<br />
21 Local/remote<br />
25 DC brake enable<br />
29 External trip<br />
Details:<br />
See P0701 (function of digital input 0).<br />
<strong>Parameter</strong> <strong>List</strong> <strong>SINAMICS</strong> <strong>G110</strong><br />
32 6SL3298-0BA11-0BP0