<strong>Parameter</strong>s <strong>04</strong>/<strong>03</strong><br />
P1134 Rounding type Min: 0<br />
CStat: CUT Datatype: U16 Unit: - Def: 0<br />
P-Group: SETPOINT Active: Immediately QuickComm.: No Max: 1<br />
Level<br />
3<br />
Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g.<br />
new setpoint, OFF1, OFF3, REV).<br />
This smoothing is applied, if the motor is ramped-up or ramped-down and<br />
- P1134 = 0,<br />
- P1130 > 0 and<br />
- the setpoint is not yet reached.<br />
P1130 > 0<br />
f Set<br />
f<br />
Setpoint reached<br />
P1134 = 0<br />
Setpoint not reached<br />
t<br />
f<br />
P1130<br />
f Set<br />
Setpoint reached<br />
P1134 = 1<br />
Setpoint not reached<br />
t<br />
ON<br />
OFF1<br />
P1130<br />
Possible Settings:<br />
0 Continuous smoothing<br />
1 Discontinuous smoothing<br />
Dependency:<br />
This parameter has no effect unless the value set in P1130 is greater than 0.<br />
P1135 OFF3 ramp-down time Min: 0.00<br />
CStat: CUT Datatype: Float Unit: s Def: 5.00<br />
P-Group: SETPOINT Active: first confirm QuickComm.: Yes Max: 650.00<br />
t<br />
Level<br />
3<br />
Defines ramp-down time from maximum frequency to standstill for OFF3 command.<br />
Settings in P1130 and P1134 will have no effect on OFF3 ramp-down characteristic. An initial ramp-down<br />
rounding time of approaximately 10% of P1135 is however included. For the total OFF3 ramp-down time:<br />
tdown,OFF3<br />
= 1.1 ⋅ P1135<br />
Note:<br />
This time may be exceeded if the VDC_max. level is reached.<br />
r1170 CO: Frequency setpoint after RFG Min: -<br />
Datatype: Float Unit: Hz Def: -<br />
P-Group: SETPOINT Max: -<br />
Displays overall frequency setpoint after ramp generator.<br />