Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
Parameter List Edition 04/03 SINAMICS G110 - Automatyka Siemens
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Parameter</strong>s <strong>04</strong>/<strong>03</strong><br />
P0731 Function of digital output 0 Min: 0<br />
CStat: CUT Datatype: U16 Unit: - Def: 5<br />
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 22<br />
Defines source of digital output 0.<br />
Possible Settings:<br />
0 Not Active<br />
1 Active<br />
2 Drive ready<br />
3 Drive ready to run<br />
4 Drive running<br />
5 Drive fault active<br />
6 OFF2 active<br />
7 OFF3 active<br />
8 Switch on inhibit active<br />
9 Drive warning active<br />
10 Deviation value<br />
11 PZD control<br />
12 Maximum frequency reached<br />
13 Warning: Motor current limit<br />
14 Motor holding brake active<br />
15 Motor overload<br />
16 Motor running direction right<br />
17 Inverter overload<br />
18 DC brake active<br />
19 Act. freq > P2167<br />
20 Act. freq > P1080 (f_min)<br />
21 Act. freq >= setpoint<br />
22 Ramping finish<br />
Note:<br />
Output of fault bit 52.3 is inverted on digital output.<br />
Details:<br />
See parameter r0052, r0053.<br />
r0747 CO/BO: State of digital outputs Min: -<br />
Datatype: U16 Unit: - Def: -<br />
P-Group: COMMANDS Max: -<br />
Level<br />
3<br />
Level<br />
3<br />
Displays status of digital outputs (also includes inversion of digital outputs via P0748).<br />
Bitfields:<br />
Bit00 Digital output 0 energized 0 NO 1 YES<br />
Dependency:<br />
Bit 0 = 0 :<br />
Optocoupler contacts open<br />
Bit 0 = 1 :<br />
Optocoupler contacts closed<br />
P0748 Invert digital outputs Min: 0<br />
CStat: CUT Datatype: U16 Unit: - Def: 0<br />
P-Group: COMMANDS Active: first confirm QuickComm.: No Max: 1<br />
Defines high and low states of relay for a given function.<br />
Bitfields:<br />
Bit00 Invert digital output 0 0 NO 1 YES<br />
r0752 Act. input of ADC Min: -<br />
Datatype: Float Unit: V Def: -<br />
P-Group: TERMINAL Max: -<br />
Level<br />
3<br />
Level<br />
3<br />
Displays smoothed analog input value in volts before the characteristic block.<br />
KL8<br />
+10 V<br />
KL9<br />
KL10<br />
A<br />
D<br />
P0753<br />
P0757<br />
P0758<br />
P0759<br />
P0760<br />
ADC<br />
scaling<br />
r0754<br />
P0761<br />
ADC<br />
dead<br />
zone<br />
P1000 = 2<br />
Setpoint<br />
r0752<br />
P07<strong>04</strong> = x<br />
1 1.7 V 0<br />
3.9 V<br />
r0722<br />
r0722.3<br />
Function<br />
<strong>Parameter</strong> <strong>List</strong> <strong>SINAMICS</strong> <strong>G110</strong><br />
34 6SL3298-0BA11-0BP0