Make external connections as shown in figure 3-10. Check<br />

after wiring to make sure all connections are correct. (Do<br />

not use the control circuit buzzer to check connections)<br />

(A) Main circuit must be separated from other high voltage<br />

or high current power line to avoid noise interference. Refer<br />

to following figures:<br />

• A noise filter in the output of the main circuit can suppress<br />

conductive noise. To prevent radiative noise, the<br />

wires should be put in a ferromagnetic metal pipe and<br />

separated from all other signal lines by at least 1ft.<br />

MCCB Metal box<br />

Metal pipe<br />

Power supply<br />

Noise<br />

Noise<br />

~ filter Filter VSC23/48<br />

M<br />

filter Filter<br />

above<br />

Signal wire<br />

Controller<br />

Fig. 6<br />

Installation examples with adjacent signal conductors<br />

• The power supply and output PE terminals must be<br />

both connected to ground to increase noise immunity of<br />

the built-in Filter.<br />

Shielded wire<br />

Protective jacket<br />

L1 L3 PE<br />

To ground terminal<br />

(refer to instructions<br />

of filter wiring)<br />

Wrapped with insulation<br />

Do not connect this end<br />

Fig. 8<br />

Processing the ends of twisted pair cables<br />

Fig. 7<br />

M<br />

T1 T2 T3<br />

Grounding filtered units<br />

(A)The control circuit wiring and main circuit wire/ other<br />

high voltage/current power wiring should be separated to<br />

avoid noise interruption.<br />

• In order to prevent noise interference which could cause<br />

VSD faults, the control circuit signal should be shielded<br />

and twisted. Please refer to fig. 8. The wiring distance<br />

should be less than 150ft (50m).<br />

PE<br />

Ground<br />

(B) Connect ground terminals as follows: (200 V class<br />

ground