Menu Function Description Range/ Code<br />
219 Remote keypad control selection<br />
000: Disable (no signal loss detection)<br />
001: Enable. On signal loss stop according to [337]<br />
002: Enable. Runs at the last set frequency. On signal loss<br />
Stop is according to [213] setting or Stop key on keypad.<br />
000<br />
Stop VSD<br />
then connect<br />
remote<br />
keypad for<br />
proper<br />
operation<br />
*4<br />
Main setup, Motor data<br />
221 Motor rated voltage *4<br />
222 Motor rated power *4<br />
223 Motor rated current *4<br />
224 Motor rated frequency *4<br />
225 Motor rated speed 0 to 120 (* 100 rpm) *4<br />
226 Carrier frequency 004 to 016 010 4 to 16K<br />
Main setup, Motor protection<br />
231 Run stall-prevention<br />
000: Run stall prevention available<br />
001: Run stall prevention unavailable<br />
000<br />
232 Run stall-prevention level (%) 050 to 300 200<br />
233 Stall prevention time during run<br />
234<br />
Electronic thermal relay protection<br />
for motor (OL1)<br />
000: according to dec. time set in [332]<br />
001: according to dec. time set in [239]<br />
000: Enable motor protection<br />
001: Disable motor protection<br />
235 Acceleration stall-prevention<br />
000: Acceleration stall prevention enable<br />
001: Acceleration stall prevention disable<br />
000<br />
236<br />
Acceleration stall-prevention level<br />
050 to 200<br />
(%)<br />
200<br />
237 Deceleration stall-prevention<br />
000: Deceleration stall prevention enable<br />
001: Deceleration stall prevention disable<br />
000<br />
238<br />
Deceleration stall-prevention level<br />
050 to 200<br />
(%)<br />
200<br />
239<br />
Stall prevention deceleration time<br />
00.1 to 999 Sec<br />
set<br />
03.0<br />
Main setup, Parameter set handling<br />
241 Copy module<br />
000: Copy module disable<br />
001: copy to module from VSD<br />
002: copy to VSD from module<br />
000 *3<br />
003: read/ write check<br />
242 Factory default<br />
010: Reset to factory default (50 Hz)<br />
020: Reset to factory default (60 Hz)<br />
000<br />
Main setup, Trip Autoreset<br />
251 Auto-restart times 000 to 005 000<br />
252 Auto Restart for power-loss<br />
000: Enable<br />
001: Disable<br />
001<br />
Main setup, Serial communication<br />
261 VSD communication address 001 to 254 001 *3 *4<br />
262 Baud rate (bps)<br />
263 Stop bit<br />
264 Parity bit<br />
000: 4800<br />
001: 9600<br />
002: 9200<br />
003: 38400<br />
000: 1 Stop bit<br />
001: 2 Stop bit<br />
000: No parity<br />
001: Even parity<br />
002: Odd parity<br />
000<br />
000<br />
Factory<br />
Default<br />
Remarks<br />
003 *3 *4<br />
000 *3 *4<br />
000 *3 *4<br />
<strong>Emotron</strong> AB 01-3993-01r3 Programming instructions and menu list 25