Safety Precautions<br />

Operation Precautions<br />

Before Power Up<br />

!<br />

!<br />

The line voltage applied must comply with<br />

the VSD’s specified input voltage. (See the<br />

nameplate)<br />

WARNING: Make sure the main circuit<br />

connections are correct. L1, L2 and L3 are<br />

power-input terminals and must not be<br />

mistaken for T1, T2 and T3. If they are, the<br />

VSD might get damaged.<br />

To avoid the front cover from disengaging, or<br />

other damage, do not carry the invertre by its<br />

covers. Support the drive by the heatsink<br />

when transporting. Improper handling can<br />

damage the inverter or injure personell and<br />

should be avoided.<br />

To avoid fire, do not install the VSD on a flammable<br />

object.<br />

During Power Up<br />

!<br />

The VSD will still stay live immediately after<br />

power loss. When the power is re-stored, the<br />

VSD operation is controlled by [252].<br />

The VSD operation is controlled by [213] and [335] and<br />

the status of (FWD/REV RUN switch) when power is restored.<br />

[33A] /[226]) Power loss ride through/Auto reset<br />

after fault).<br />

1. When [213]=000, the VSD will not auto restart when<br />

power is re-stored.<br />

2. When [213]=001 and operation switches (FWD/REV<br />

RUN) is OFF, the VSD will not auto restart when power is<br />

re-stored.<br />

3. When [213]=001and operation switch ON and<br />

[335]=000, the VSD will auto restart when power is restored.<br />

Please turn OFF the run (start) switch to avoid<br />

damage to machine and injury to personnel before the<br />

power is re-stored.<br />

When [335]=000 (direct start on power up), please refer<br />

to the description and warning for [335] to verify the<br />

safety of operator and machine.<br />

If several VSD’s are placed in the same control panel,<br />

assure that the temperature stays below 50°C to avoid<br />

overheating or fire.<br />

<strong>Emotron</strong> AB 01-3993-01r3 3