[252]=000: Auto restart after a momentary power loss is<br />
enabled on resumption of power and applying the run signal,<br />
according to setting of menu [213].<br />
The VSD will carry out an auto speed search, once the<br />
motor rotation speed is found then it will accelerate to the<br />
running speed it had before the power loss.<br />
[252]=001: Disable<br />
261 VSD communication address: 001 to 254<br />
[261] set communication address, for the specific VSD<br />
when multi-VSDs are controlled by communication<br />
method.<br />
262 Baud rate (bps)<br />
000: 4800<br />
001: 9600<br />
002: 19200<br />
003: 38400<br />
263 Stop bit<br />
000: 1 Stop bit<br />
001: 2 Stop bit<br />
264 Parity bit<br />
000: No parity<br />
001: Even parity<br />
002: Odd parity<br />
265 Data bits<br />
000: 8 bits data<br />
001: 7 bits data<br />
1. RS-485 communication: (requires RS485 port device)<br />
1 to 1 control: PC or PLC or controller controls one<br />
VSD ([261] is set to 001 to 254).<br />
1 to multiple drives control: PC or PLC or other controllers<br />
control several VSDs (the maximum number of<br />
units which can be controlled is 32). When the communication<br />
address =000, the VSD is controlled by communication<br />
regardless of the [261] setting.<br />
2. RS-232communication: (requires RS232 port)<br />
1 to 1 control: PC or PLC or controller controls one<br />
VSD ([261] is set to 001 to 254).<br />
NOTE: a. The Baud rate [262] and communication format<br />
([263]/[264]/[265]) of the PC (or PLC or other<br />
controller) and VSD should be the same.<br />
b. The VSD will validate the modified parameters after<br />
the parameters modified in the PC.<br />
c. Communication protocol: refer to EV communication<br />
protocol description.<br />
d. Parameter [261] to [265] can’t be changed via<br />
communication module<br />
266 Communication Time out detection time<br />
Time-out detection time: 00.0 to 25.5sec; setting 00.0 sec:<br />
disable time-out function.<br />
Default: 00.0 sec<br />
Communication time-out detection is independent of<br />
RUN/Frequency command.<br />
*Cannot be modified during communication.<br />
267 Communication Time out operation selection<br />
Time-out operation selection:<br />
000: Deceleration to stop ([332]: Deceleration time 1).<br />
001: Free run to stop.<br />
002: Deceleration to stop ([334]: Deceleration time 2).<br />
003: Continue operating.<br />
Default=000<br />
Reset method:<br />
a. Use the Reset key<br />
b. Receive correct data from the master.<br />
NOTE: After communication time-out the motor<br />
decelerates to stop ([267]=000,001,002). The motor will<br />
not start unless a new RUN command is given according<br />
to [213].<br />
*Cannot be modified during communication.<br />
[266]/[267] Communication time out parameter timing<br />
pattern.<br />