Menu Function Description Range/ Code<br />

Process and application parameters, Preset references<br />

361<br />

Frequency Up/ Down control<br />

using MFIT<br />

000: Up/Down command is available. Set frequency is held<br />

when VSD stops.<br />

001: Up/Down command is available. Set frequency resets<br />

to 0Hz when VSD stops.<br />

002: Up/Down command is available. Set frequency is held<br />

when VSD stops. Up/Down is available in stop.<br />

362<br />

Preset frequency 1 (Main frequency<br />

setting)<br />

00.0 to 200 Hz 05.0 *1<br />

363 Preset frequency 2 00.0 to 200 Hz 05.0 *1<br />

364 Preset frequency 3 00.0 to 200 Hz 10.0 *1<br />

365 Preset frequency 4 00.0 to 200 Hz 20.0 *1<br />

366 Preset frequency 5 00.0 to 200 Hz 30.0 *1<br />

367 Preset frequency 6 00.0 to 200 Hz 40.0 *1<br />

368 Preset frequency 7 00.0 to 200 Hz 50.0 *1<br />

369 Preset frequency 8 00.0 to 200 Hz 60.0 *1<br />

Process and application parameters, PID Process control<br />

381 PID operation mode<br />

000<br />

000: PID Function unavailable<br />

001: PID control, Bias D control<br />

002: PID Control, Feedback D control<br />

000<br />

003: PID Control, Bias D reverse characteristics control.<br />

004: PID Control, feedback D reverse characteristics control.<br />

382 PID OFFSET<br />

000: Positive direction<br />

001: Negative direction<br />

000 *1<br />

383 P: Proportional gain 0.00 to 10.0 01.0 *1<br />

384 I: Integral time (s) 00.0 to 100 10.0 *1<br />

385 D: Differential time (s) 0.00 to 10.0 0.00 *1<br />

Load monitor<br />

411 Alarm Select<br />

412 Alarm Trip<br />

000: Off<br />

001: Min<br />

002: Max<br />

003: Min+Max<br />

000: Off<br />

001: Min<br />

002: Max<br />

003: Min+Max<br />

Factory<br />

Default<br />

000 *1<br />

000 *1<br />

413 Ramp Alarm<br />

000: Off<br />

001: On<br />

000 *1<br />

414 Alarm Start Delay 0 to 999 s 002 *1<br />

415 Load Type<br />

000: Basic<br />

001: Load Curve<br />

000 *1<br />

416 Max Alarm Margin 0 to 400% 015 *1<br />

417 Max Alarm Delay 0 to 90 s 01.0 *1<br />

418 Max Pre-Alarm Margin 0 to 400% 010 *1<br />

419 Max Pre-Alarm Delay 0 to 90 s 01.0 *1<br />

41A Min Pre-Alarm Margin 0 to 400% 010 *1<br />

41B Min Pre-Alarm Delay 0 to 90 s 01.0 *1<br />

41C Min Alarm Margin 0 to 400% 010 *1<br />

41D Min Alarm Delay 0 to 90 s 01.0 *1<br />

41E AutoSet Alarm<br />

000: No<br />

001: Yes<br />

000 *1<br />

41F Normal Load 0 to 400% of max torque 100 *1<br />

Remarks<br />