Rendamax<br />

5.3.4.2 Air supply pipe<br />

<strong>The</strong> air supply pipe may be single-walled and constructed of:<br />

- plastic<br />

- thin-walled aluminium<br />

- flexible aluminium (take account of the resistance)<br />

- stainless steel.<br />

Fig. 5<br />

horizontal air supply<br />

Type<br />

R301<br />

R302<br />

R303<br />

R304<br />

R305<br />

R306<br />

R307<br />

Air supply diameter D1 (mm)<br />

100<br />

100<br />

125<br />

125<br />

150<br />

180<br />

180<br />

Table 4<br />

Air supply connection<br />

<strong>The</strong> connection to the air supply pipe is always mounted on the back of the unit.<br />

Multiple units may not be connected to the same air supply or flue pipe.<br />

To prevent snow entering, the air supply pipe must extend at least 300 mm above the roof and<br />

must be fitted with a rain cap.<br />

<strong>The</strong> flue pipe opening must end at least 1000 mm above the roof, assuming the roof to be flat.<br />

Doc586/50CV22C 17