Rendamax<br />
5.3.4.2 Air supply pipe<br />
<strong>The</strong> air supply pipe may be single-walled and constructed of:<br />
- plastic<br />
- thin-walled aluminium<br />
- flexible aluminium (take account of the resistance)<br />
- stainless steel.<br />
Fig. 5<br />
horizontal air supply<br />
Type<br />
R301<br />
R302<br />
R303<br />
R304<br />
R305<br />
R306<br />
R307<br />
Air supply diameter D1 (mm)<br />
100<br />
100<br />
125<br />
125<br />
150<br />
180<br />
180<br />
Table 4<br />
Air supply connection<br />
<strong>The</strong> connection to the air supply pipe is always mounted on the back of the unit.<br />
Multiple units may not be connected to the same air supply or flue pipe.<br />
To prevent snow entering, the air supply pipe must extend at least 300 mm above the roof and<br />
must be fitted with a rain cap.<br />
<strong>The</strong> flue pipe opening must end at least 1000 mm above the roof, assuming the roof to be flat.<br />
Doc586/50CV22C 17