Rendamax<br />
2 Installation<br />
2.1 Connections<br />
2.1.1 Electrical connection<br />
Electro-technical data<br />
Type<br />
Fan, control and<br />
safety components<br />
R301<br />
R302<br />
R303<br />
R304<br />
R305<br />
R306<br />
R307<br />
Supply*<br />
1N~<br />
Power<br />
consumption<br />
(max)<br />
Supply*<br />
1N~<br />
Pump<br />
Power<br />
consumption<br />
(max)<br />
Total electrical<br />
power<br />
consumption<br />
(max)<br />
V W V W W<br />
230<br />
230<br />
230<br />
230<br />
230<br />
230<br />
230<br />
128<br />
128<br />
391<br />
391<br />
397<br />
397<br />
397<br />
230<br />
230<br />
230<br />
230<br />
230<br />
230<br />
230<br />
60<br />
90<br />
90<br />
90<br />
90<br />
245<br />
245<br />
188<br />
218<br />
481<br />
481<br />
487<br />
642<br />
642<br />
Table 5<br />
Electrotechnical data<br />
* tolerance on voltage 230 V +10% /-15%<br />
tolerance on frequency 50 Hz Å5%<br />
** the stated pump power is based on the maximum power con sumption in pump speed 3.<br />
2.1.2 Water connections<br />
<strong>The</strong> pump installed in the bypass supplies the required head and capacity for the burner, 1 st heat<br />
exchanger and 2nd heat exchanger and overcomes the resistance of these three parts.<br />
<strong>The</strong> pump does not replace the system pumps!<br />
2.1.3 Condensate discharge<br />
<strong>The</strong> appliance is fitted with a water trap which prevents flue gasses from entering the boiler room.<br />
Ensure that the distance between the condensate discharge point of the boiler trap and the drainage<br />
pipe ia at least 5 mm.<br />
Fig. 4<br />
Condensate discharge<br />
48 Doc586/50CV22C