Rendamax<br />

Where: ∅ = the diameter of the low velocity header in mm<br />

Q = the water flow rate in m 3 /h of the boiler circuit or the secondary circuit, whichever<br />

is the greater<br />

v = the s peed in m/s .<br />

Example of a low velocity header with isolating valves and an expansion tank.<br />

Fig. 12<br />

Installation with a low velocity header, isolating valves and expansion tanks<br />

Mounting the low velocity header vertically has additional advantages: the upper section functions<br />

as an air separator and the lower section serves as a dirt seperator.<br />

When air heaters (for ventilation or air treatment) are included in the system it is generally desirable<br />

to have a small ∆T over the air heaters. Because of this, the water flow rate through the whole<br />

secondary circuit is usually greater than that through the boilers. <strong>The</strong> low velocity header must<br />

be so dimensioned that the water speed does not exceed 0.5 m/s. In this case the diameter of the<br />

low velocity header must be calculated on the basis of the water flow through the secondary circuit.<br />

Because the volume of the water in the secondary system is greater than that in the primary<br />

circuit (boiler), there will be a water circulation in the opposite direction to that of the primary<br />

circulation through the low velocity header. A mixed temperature will then exist which is lower<br />

than the supply temperature from the boiler. <strong>The</strong> regulation system will react to this and will open<br />

the regulator functions (valves, etc.) in the system. Generally, the temperature of the water supply<br />

from the boiler(s) will need to be corrected to obtain the desired temperature in the connected<br />

circuits.<br />

Systems with a separate flow header and a return header<br />

Flow headers in combination with return headers are often used in renovation projects. Several<br />

circuits operate with mixing valves or diverting valves. In both cases a low velocity header or a<br />

bypass is necessary.<br />

Doc586/50CV22C 27