Where: ∅ = the diameter of the low velocity header in mm<br />
Q = the water flow rate in m 3 /h of the boiler circuit or the secondary circuit, whichever<br />
is the greater<br />
v = the s peed in m/s .<br />
Example of a low velocity header with isolating valves and an expansion tank.<br />
Fig. 12<br />
Installation with a low velocity header, isolating valves and expansion tanks<br />
Mounting the low velocity header vertically has additional advantages: the upper section functions<br />
as an air separator and the lower section serves as a dirt seperator.<br />
When air heaters (for ventilation or air treatment) are included in the system it is generally desirable<br />
to have a small ∆T over the air heaters. Because of this, the water flow rate through the whole<br />
secondary circuit is usually greater than that through the boilers. <strong>The</strong> low velocity header must<br />
be so dimensioned that the water speed does not exceed 0.5 m/s. In this case the diameter of the<br />
low velocity header must be calculated on the basis of the water flow through the secondary circuit.<br />
Because the volume of the water in the secondary system is greater than that in the primary<br />
circuit (boiler), there will be a water circulation in the opposite direction to that of the primary<br />
circulation through the low velocity header. A mixed temperature will then exist which is lower<br />
than the supply temperature from the boiler. <strong>The</strong> regulation system will react to this and will open<br />
the regulator functions (valves, etc.) in the system. Generally, the temperature of the water supply<br />
from the boiler(s) will need to be corrected to obtain the desired temperature in the connected<br />
circuits.<br />
Systems with a separate flow header and a return header<br />
Flow headers in combination with return headers are often used in renovation projects. Several<br />
circuits operate with mixing valves or diverting valves. In both cases a low velocity header or a<br />
bypass is necessary.<br />