Rendamax<br />

2.3 Examples of hydraulic Systems<br />

<strong>The</strong> hydraulic systems shown are only examples. <strong>The</strong>y must not be employed in practice without<br />

professional analysis.<br />

Figure 9 shows an example of an R300 unit with a bypass in a system with one heating circuit<br />

only. As the bypass pump returns only a little quantity of flow water to the unit in case of a ∆T of<br />

20°C the boiler resistance is hardly any higher then with a conventional unit without a bypass. <strong>The</strong><br />

choice of a system pump can be made according to the known boiler resistances.<br />

Fig. 8<br />

R300 Bypass - one heating circuit<br />

An example of a system with more heating circuits is shown in figure 10. In this case the application<br />

of an open header is not necessary, because it’s replaced by the bypass. Using a closed<br />

header is to be advised. Application of a pump between the unit and the header is not necessary a<br />

system pumps supply the required water flow through the unit.<br />

Fig. 10<br />

R300 Bypass - heating groups<br />

Doc586/50CV22C 51