Rendamax<br />
1 Description<br />
1.1 General<br />
In case the water volume flow over the unit is too low (high ∆T) this bypass directly returns flow<br />
water to the secondary heat exchanger and thereby guarantees the minimum required flow in the<br />
unit.<br />
<strong>The</strong> pump installed in the bypass supplies the required head and capacity for the burner, 1 st heat<br />
exchanger and the 2 nd heat exchanger and overcomes the resistance of these three parts. With a<br />
high water flow (low ∆T) the pump only supplies little of it’s capacity as the volume flow complies<br />
with the minimum required flow quantity. However a low water volume flow (high ∆T) forces the<br />
pump to supply such a force that the minimum required flow over the unit is guaranteed.<br />
<strong>The</strong> Rendamax unit equipped with a bypass and bypass pump supplies no remaining head for the<br />
heating circuits. Further the bypass pump does not replace the system pumps and should not be<br />
used for that purpose. <strong>The</strong> pump has to be switched in position 3 for all unit types.<br />