Rendamax<br />

1 Description<br />

1.1 General<br />

In case the water volume flow over the unit is too low (high ∆T) this bypass directly returns flow<br />

water to the secondary heat exchanger and thereby guarantees the minimum required flow in the<br />

unit.<br />

<strong>The</strong> pump installed in the bypass supplies the required head and capacity for the burner, 1 st heat<br />

exchanger and the 2 nd heat exchanger and overcomes the resistance of these three parts. With a<br />

high water flow (low ∆T) the pump only supplies little of it’s capacity as the volume flow complies<br />

with the minimum required flow quantity. However a low water volume flow (high ∆T) forces the<br />

pump to supply such a force that the minimum required flow over the unit is guaranteed.<br />

<strong>The</strong> Rendamax unit equipped with a bypass and bypass pump supplies no remaining head for the<br />

heating circuits. Further the bypass pump does not replace the system pumps and should not be<br />

used for that purpose. <strong>The</strong> pump has to be switched in position 3 for all unit types.<br />

Fig. 2<br />

<strong>The</strong> Rendamax R300<br />

Doc586/50CV22C 45