Rendamax<br />

<strong>The</strong> following table lists all the flue gas data for all types.<br />

Type<br />

R301<br />

R302<br />

R303<br />

R304<br />

R305<br />

R306<br />

R307<br />

Flue gas temperature<br />

at full<br />

capacity<br />

(approx.)<br />

Flue gas quantity at full capacity<br />

Maximum permissible<br />

chimney<br />

resistance<br />

°C m 3 /h kg/s mbar<br />

≈ 135<br />

≈ 135<br />

≈ 135<br />

≈ 135<br />

≈ 135<br />

≈ 135<br />

≈ 135<br />

130<br />

161<br />

214<br />

261<br />

345<br />

430<br />

513<br />

0.033<br />

0.040<br />

0.053<br />

0.065<br />

0.086<br />

0.106<br />

0.127<br />

1.8<br />

1.8<br />

1.0<br />

1.0<br />

1.0<br />

1.0<br />

1.0<br />

Table 5<br />

Flue gas data<br />

Capacity 100%<br />

Flow temperature 80°C<br />

Return temperature<br />

60°C.<br />

5.3.5.2 Chimney<br />

Chimney length<br />

Because the appliance is fitted with a “premix burner” with a fan, an over-pressure is built up in<br />

the unit. This overpressure is sufficient to overcome the resistance of the cooled burner, heat exchangers,<br />

air intake and chimney up to a maximum of 1.8 mbar (types 1 and 2) or 1.0 mbar (types 3<br />

to 7) external to the boiler.<br />

<strong>The</strong> back-pressure outside the unit depends on:<br />

a <strong>The</strong> resistance of the flue pipe<br />

b <strong>The</strong> degree of cooling of the burner system<br />

c <strong>The</strong> resistance of the discharge system.<br />

<strong>The</strong> degree of cooling of the flue gasses depends on:<br />

a the insulation value of the chimney<br />

b the local ambient temperature<br />

c the discharge system.<br />

<strong>The</strong> flue connection diameters of the units have been chosen such that the speed of the flue gas<br />

will always be approximately 5 m/s. For the appliance there will be a maximum overpressure of<br />

approximately 1.8 mbar (types 1 and 2) or 1.0 mbar (types 3 to 7) for the flue system.<br />

y<br />

Owing to their high resistance, bends with an R/D ratio smaller than 1 should be avoided.<br />

Calculation of the diameter and length<br />

For calculating and checking the internal diameter of a flue system with mechanical discharge,<br />

refer to the applicable national and local regulations and specifications.<br />

Doc586/50CV22C 19