Rendamax<br />
<strong>The</strong> following table lists all the flue gas data for all types.<br />
Type<br />
R301<br />
R302<br />
R303<br />
R304<br />
R305<br />
R306<br />
R307<br />
Flue gas temperature<br />
at full<br />
capacity<br />
(approx.)<br />
Flue gas quantity at full capacity<br />
Maximum permissible<br />
chimney<br />
resistance<br />
°C m 3 /h kg/s mbar<br />
≈ 135<br />
≈ 135<br />
≈ 135<br />
≈ 135<br />
≈ 135<br />
≈ 135<br />
≈ 135<br />
130<br />
161<br />
214<br />
261<br />
345<br />
430<br />
513<br />
0.033<br />
0.040<br />
0.053<br />
0.065<br />
0.086<br />
0.106<br />
0.127<br />
1.8<br />
1.8<br />
1.0<br />
1.0<br />
1.0<br />
1.0<br />
1.0<br />
Table 5<br />
Flue gas data<br />
Capacity 100%<br />
Flow temperature 80°C<br />
Return temperature<br />
60°C.<br />
5.3.5.2 Chimney<br />
Chimney length<br />
Because the appliance is fitted with a “premix burner” with a fan, an over-pressure is built up in<br />
the unit. This overpressure is sufficient to overcome the resistance of the cooled burner, heat exchangers,<br />
air intake and chimney up to a maximum of 1.8 mbar (types 1 and 2) or 1.0 mbar (types 3<br />
to 7) external to the boiler.<br />
<strong>The</strong> back-pressure outside the unit depends on:<br />
a <strong>The</strong> resistance of the flue pipe<br />
b <strong>The</strong> degree of cooling of the burner system<br />
c <strong>The</strong> resistance of the discharge system.<br />
<strong>The</strong> degree of cooling of the flue gasses depends on:<br />
a the insulation value of the chimney<br />
b the local ambient temperature<br />
c the discharge system.<br />
<strong>The</strong> flue connection diameters of the units have been chosen such that the speed of the flue gas<br />
will always be approximately 5 m/s. For the appliance there will be a maximum overpressure of<br />
approximately 1.8 mbar (types 1 and 2) or 1.0 mbar (types 3 to 7) for the flue system.<br />
y<br />
Owing to their high resistance, bends with an R/D ratio smaller than 1 should be avoided.<br />
Calculation of the diameter and length<br />
For calculating and checking the internal diameter of a flue system with mechanical discharge,<br />
refer to the applicable national and local regulations and specifications.<br />