Rendamax<br />

2.2 Hydraulic system<br />

2.2.1 General<br />

Although it is not the intention to provide a complete handbook covering the most divergent<br />

hydraulic systems, the data is more extensive than would generally be provided in the case of<br />

conventional central heating boilers.<br />

2.2.2 Water flow<br />

Table 6 lists the required relationship between the three parameters Q (water flow), P (pressure)<br />

and t (temperature) at maximum capacity. Because of the high flow rate, the appliance is less<br />

sensitive to water hardness. <strong>The</strong>refore, the water hardness may not exceed 250 ppm with a supply<br />

temperature of 80 °C.<br />

2.2.2.1 Flow rate and resistance<br />

Type Dt 22 K Pump data<br />

R301<br />

R302<br />

R303<br />

R304<br />

R305<br />

R306<br />

R307<br />

Nominal<br />

flow rate<br />

Boilerresistance<br />

Grundfos<br />

pump type<br />

Pump<br />

speed<br />

Max. power<br />

consumption<br />

m 3 /h kPa UPS W<br />

2.72<br />

3.51<br />

4.52<br />

5.48<br />

7.25<br />

9.05<br />

10.85<br />

17.0<br />

23.5<br />

30.0<br />

30.0<br />

20.0<br />

23.0<br />

32.0<br />

32-40<br />

32-60<br />

32-60<br />

32-60<br />

32-60<br />

32-80<br />

32-80<br />

3<br />

3<br />

3<br />

3<br />

3<br />

3<br />

3<br />

60<br />

90<br />

90<br />

90<br />

90<br />

245<br />

245<br />

Table 6<br />

Water flow rate and pump data R300<br />

* <strong>The</strong> maximum power consumption of the pump is given for pump speed 3.<br />

<strong>The</strong> pump has to be switched in position 3 for all unit types.<br />

<strong>The</strong> unit has a standard pump control. When the boiler is enabled, the pump is switched on. When<br />

the enable signal is removed, the pump will continu to run for several minutes. This run is on time<br />

adjustable. <strong>The</strong> standard time is two seconds.<br />

2.2.2.2 Pump characteristics<br />

Fig. 5 Pump characteristic UPS 32-40<br />

Doc586/50CV22C 49