2.2 Hydraulic system<br />
2.2.1 General<br />
Although it is not the intention to provide a complete handbook covering the most divergent<br />
hydraulic systems, the data is more extensive than would generally be provided in the case of<br />
conventional central heating boilers.<br />
2.2.2 Water flow<br />
Table 6 lists the required relationship between the three parameters Q (water flow), P (pressure)<br />
and t (temperature) at maximum capacity. Because of the high flow rate, the appliance is less<br />
sensitive to water hardness. <strong>The</strong>refore, the water hardness may not exceed 250 ppm with a supply<br />
temperature of 80 °C.<br />
2.2.2.1 Flow rate and resistance<br />
Type Dt 22 K Pump data<br />
R301<br />
R302<br />
R303<br />
R304<br />
R305<br />
R306<br />
R307<br />
Nominal<br />
flow rate<br />
Boilerresistance<br />
Grundfos<br />
pump type<br />
Pump<br />
speed<br />
Max. power<br />
consumption<br />
m 3 /h kPa UPS W<br />
2.72<br />
3.51<br />
4.52<br />
5.48<br />
7.25<br />
9.05<br />
10.85<br />
17.0<br />
23.5<br />
30.0<br />
30.0<br />
20.0<br />
23.0<br />
32.0<br />
32-40<br />
32-60<br />
32-60<br />
32-60<br />
32-60<br />
32-80<br />
32-80<br />
3<br />
3<br />
3<br />
3<br />
3<br />
3<br />
3<br />
60<br />
90<br />
90<br />
90<br />
90<br />
245<br />
245<br />
Table 6<br />
Water flow rate and pump data R300<br />
* <strong>The</strong> maximum power consumption of the pump is given for pump speed 3.<br />
<strong>The</strong> pump has to be switched in position 3 for all unit types.<br />
<strong>The</strong> unit has a standard pump control. When the boiler is enabled, the pump is switched on. When<br />
the enable signal is removed, the pump will continu to run for several minutes. This run is on time<br />
adjustable. <strong>The</strong> standard time is two seconds.<br />
2.2.2.2 Pump characteristics<br />
Fig. 5 Pump characteristic UPS 32-40<br />
Doc586/50CV22C 49