Vibra Trol ® Data<br />

Selection<br />

Disturbing<br />

Frequency<br />

Isolator Deflection<br />

(RPM) 1 /16" 1 /8" 1 /4" 1 /2" 1" 2"<br />

250-299 N/R N/R N/R N/R N/R N/R<br />

300-349 N/R N/R N/R N/R N/R 76%<br />

350-399 N/R N/R N/R N/R N/R 83%<br />

400-449 N/R N/R N/R N/R 74% 87%<br />

450-499 N/R N/R N/R N/R 79% 90%<br />

500-599 N/R N/R N/R N/R 83% 92%<br />

600-699 N/R N/R N/R 75% 89% 95%<br />

700-799 N/R N/R N/R 83% 92% 96%<br />

800-899 N/R N/R N/R 87% 94% 97%<br />

900-999 N/R N/R 78% 90% 95% 98%<br />

1000-1099 N/R N/R 83% 92% 96% 98%<br />

1100-1199 N/R N/R 86% 94% 97% 99%<br />

1200-1299 N/R 83% 89% 95% 97% 99%<br />

1300-1399 N/R 86% 91% 97% 98% 99%<br />

1400-1499 N/R 89% 92% 97% 98% 99%<br />

1500-1599 N/R 90% 93% 97% 99% 99%<br />

1600-1699 N/R 91% 94% 97% 99% 99%<br />

1700-1799 75% 93% 95% 97% 99% 99%<br />

1800-1899 78% 93% 95% 98% 99% 99%<br />

1900-1999 80% 94% 96% 98% 99% 99%<br />

2000-2249 82% 95% 96% 98% 99% 99%<br />

2250-2499 85% 95% 97% 98% 99% 99%<br />

2500-2999 87% 96% 97% 98% 99% 99%<br />

3000-3499 88% 97% 98% 99% 99% 99%<br />

3500-3999 90% 98% 98% 99% 99% 99%<br />

V<br />

I<br />

B<br />

R<br />

A<br />

T<br />

I<br />

O<br />

N<br />

I<br />

S<br />

O<br />

L<br />

A<br />

T<br />

I<br />

O<br />

N<br />

Critical Installations 96% to 99% Vibration Isolation<br />

Efficiency recommended (only 1% to 4% of disturbing<br />

vibration transmitted).<br />

Typical installations: TV and Radio Broadcast Studios,<br />

Concert Halls, Libraries, Churches, Hospitals, Schools and<br />

Universities, Hotels, Private Offices, Theaters, Recording<br />

Studios<br />

Standard Installations 90% to 95% Vibration Isolation<br />

Efficiency recommended (only 5% to 10% of disturbing<br />

vibration transmitted).<br />

Typical installations: Computer Equipment Areas,<br />

Restaurants, Shopping Malls, Gymnasiums, Health Clubs<br />

and Spas, Sports Arenas, Indoor Swimming Pools, Building<br />

Service Areas, Night Clubs, General Office Buildings<br />

Non-Critical Installations 75% to 89% Vibration<br />

Isolation Efficiency recommended (only 11% to 24% of<br />

disturbing vibration transmitted).<br />

Typical installations: In factory Offices, Motor Vehicle<br />

Inspection Stations and Facilities, Laundramats, Roller and<br />

Ice Skating Rinks, Factory Production Areas<br />

For 1 /16" (1.6) deflection: Specify B-<strong>Line</strong> series NNP Ribbed<br />

Neoprene Pads.<br />

For 1 /8" (3.2) deflection: Specify B-<strong>Line</strong> series CNP<br />

Combination Cork and Ribbed Neoprene Pads or B-<strong>Line</strong><br />

Series VRP Pads.<br />

For 1 /4" (6.3) deflection: Specify B-<strong>Line</strong> series N Neoprene<br />

Mountings or B-<strong>Line</strong> series RH Neoprene <strong>Hangers</strong>.<br />

For 1 /2" (12.7) deflection: Specify B-<strong>Line</strong> series ND<br />

Neoprene Mountings or B-<strong>Line</strong> series RH Neoprene<br />

<strong>Hangers</strong>.<br />

For 1"-2" (25.4-50.8) deflection: Specify B-<strong>Line</strong> series HM<br />

Housed Spring Mountings or B-<strong>Line</strong> series OM Open Spring<br />

Mountings or B-<strong>Line</strong> series HS Spring <strong>Hangers</strong>.<br />

N/R = Not Recommended<br />

E<br />

F<br />

F<br />

I<br />

C<br />

I<br />

E<br />

N<br />

C<br />

Y<br />

Vibra Trol<br />

For larger deflection requirements, consult factory.<br />

Proper Sizing<br />

Once it is determined as to what type of vibration dampening device is needed, weight loading is the next<br />

crucial step. As a built in safety measure, take the actual weight of supported pipe or equipment (consider all<br />

accessories - i.e. valves, insulation, brackets, etc...) and multiply by 1.25. Then refer to the sizing chart for the<br />

selected product to determine part number.<br />

Sizing: Divide weight of equipment by points of support to determine load requirement per support.<br />

Example: 240 Lb. (90.7 kg) piece of equipment, 4 support points, take 240 x 1.25 = 300 Lbs. (136.1 kg)<br />

(safety measure), then take 300 ÷ 4 = 75 Lbs. (34.0 kg) Specify appropriate vibration device rated at<br />

75 Lbs. (34.0 kg) for each of the support points.<br />

If weight of equipment is unequally proportionate, select mounts to satisfy the weight distribution.<br />

All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.<br />