Cooper B-Line Pipe Hangers & Supports - Dixie Construction Products
Cooper B-Line Pipe Hangers & Supports - Dixie Construction Products
Cooper B-Line Pipe Hangers & Supports - Dixie Construction Products
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Vibra Trol ® Data<br />
Selection<br />
Disturbing<br />
Frequency<br />
Isolator Deflection<br />
(RPM) 1 /16" 1 /8" 1 /4" 1 /2" 1" 2"<br />
250-299 N/R N/R N/R N/R N/R N/R<br />
300-349 N/R N/R N/R N/R N/R 76%<br />
350-399 N/R N/R N/R N/R N/R 83%<br />
400-449 N/R N/R N/R N/R 74% 87%<br />
450-499 N/R N/R N/R N/R 79% 90%<br />
500-599 N/R N/R N/R N/R 83% 92%<br />
600-699 N/R N/R N/R 75% 89% 95%<br />
700-799 N/R N/R N/R 83% 92% 96%<br />
800-899 N/R N/R N/R 87% 94% 97%<br />
900-999 N/R N/R 78% 90% 95% 98%<br />
1000-1099 N/R N/R 83% 92% 96% 98%<br />
1100-1199 N/R N/R 86% 94% 97% 99%<br />
1200-1299 N/R 83% 89% 95% 97% 99%<br />
1300-1399 N/R 86% 91% 97% 98% 99%<br />
1400-1499 N/R 89% 92% 97% 98% 99%<br />
1500-1599 N/R 90% 93% 97% 99% 99%<br />
1600-1699 N/R 91% 94% 97% 99% 99%<br />
1700-1799 75% 93% 95% 97% 99% 99%<br />
1800-1899 78% 93% 95% 98% 99% 99%<br />
1900-1999 80% 94% 96% 98% 99% 99%<br />
2000-2249 82% 95% 96% 98% 99% 99%<br />
2250-2499 85% 95% 97% 98% 99% 99%<br />
2500-2999 87% 96% 97% 98% 99% 99%<br />
3000-3499 88% 97% 98% 99% 99% 99%<br />
3500-3999 90% 98% 98% 99% 99% 99%<br />
V<br />
I<br />
B<br />
R<br />
A<br />
T<br />
I<br />
O<br />
N<br />
I<br />
S<br />
O<br />
L<br />
A<br />
T<br />
I<br />
O<br />
N<br />
Critical Installations 96% to 99% Vibration Isolation<br />
Efficiency recommended (only 1% to 4% of disturbing<br />
vibration transmitted).<br />
Typical installations: TV and Radio Broadcast Studios,<br />
Concert Halls, Libraries, Churches, Hospitals, Schools and<br />
Universities, Hotels, Private Offices, Theaters, Recording<br />
Studios<br />
Standard Installations 90% to 95% Vibration Isolation<br />
Efficiency recommended (only 5% to 10% of disturbing<br />
vibration transmitted).<br />
Typical installations: Computer Equipment Areas,<br />
Restaurants, Shopping Malls, Gymnasiums, Health Clubs<br />
and Spas, Sports Arenas, Indoor Swimming Pools, Building<br />
Service Areas, Night Clubs, General Office Buildings<br />
Non-Critical Installations 75% to 89% Vibration<br />
Isolation Efficiency recommended (only 11% to 24% of<br />
disturbing vibration transmitted).<br />
Typical installations: In factory Offices, Motor Vehicle<br />
Inspection Stations and Facilities, Laundramats, Roller and<br />
Ice Skating Rinks, Factory Production Areas<br />
For 1 /16" (1.6) deflection: Specify B-<strong>Line</strong> series NNP Ribbed<br />
Neoprene Pads.<br />
For 1 /8" (3.2) deflection: Specify B-<strong>Line</strong> series CNP<br />
Combination Cork and Ribbed Neoprene Pads or B-<strong>Line</strong><br />
Series VRP Pads.<br />
For 1 /4" (6.3) deflection: Specify B-<strong>Line</strong> series N Neoprene<br />
Mountings or B-<strong>Line</strong> series RH Neoprene <strong>Hangers</strong>.<br />
For 1 /2" (12.7) deflection: Specify B-<strong>Line</strong> series ND<br />
Neoprene Mountings or B-<strong>Line</strong> series RH Neoprene<br />
<strong>Hangers</strong>.<br />
For 1"-2" (25.4-50.8) deflection: Specify B-<strong>Line</strong> series HM<br />
Housed Spring Mountings or B-<strong>Line</strong> series OM Open Spring<br />
Mountings or B-<strong>Line</strong> series HS Spring <strong>Hangers</strong>.<br />
N/R = Not Recommended<br />
E<br />
F<br />
F<br />
I<br />
C<br />
I<br />
E<br />
N<br />
C<br />
Y<br />
Vibra Trol<br />
For larger deflection requirements, consult factory.<br />
Proper Sizing<br />
Once it is determined as to what type of vibration dampening device is needed, weight loading is the next<br />
crucial step. As a built in safety measure, take the actual weight of supported pipe or equipment (consider all<br />
accessories - i.e. valves, insulation, brackets, etc...) and multiply by 1.25. Then refer to the sizing chart for the<br />
selected product to determine part number.<br />
Sizing: Divide weight of equipment by points of support to determine load requirement per support.<br />
Example: 240 Lb. (90.7 kg) piece of equipment, 4 support points, take 240 x 1.25 = 300 Lbs. (136.1 kg)<br />
(safety measure), then take 300 ÷ 4 = 75 Lbs. (34.0 kg) Specify appropriate vibration device rated at<br />
75 Lbs. (34.0 kg) for each of the support points.<br />
If weight of equipment is unequally proportionate, select mounts to satisfy the weight distribution.<br />
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.<br />
169