Download - TDK-Lambda
Download - TDK-Lambda
Download - TDK-Lambda
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Specifications Genesys GEN / GENH 750 / 1500 W<br />
Interface RS-232 & RS-485 or Optional GPIB / LAN Interface<br />
Model 6 8 12.5 20<br />
Remote Current Programming (16 bit) (750 W)<br />
Resolution (0.012 % of lo Rated) [mA] 12 10.8 7.2 4.56<br />
Accuracy (0.1 % lo Rated + 0.1 % of lo Actual Output) [mA] 200 180 120 76<br />
Readback Current (750 W)<br />
Resolution (0.012 % of lo Rated) [mA] 12 10.8 7.2 4.56<br />
Accuracy (0.3 % lo Rated + 0.1 % of lo Actual Output) [mA] 400 360 240 152<br />
Remote Current Programming (16 bit) (1500 W)<br />
Resolution (0.012 % of lo Rated) [mA] 24 21.6 14.4 9.12<br />
Accuracy (0.1 % lo Rated + 0.1 % of lo Actual Output) [mA] 400 360 240 152<br />
Readback Current (1500 W)<br />
Resolution (0.012 % of lo Rated) [mA] 24 21.6 14.4 9.12<br />
Accuracy (0.3 % lo Rated + 0.1 % of lo Actual Output) [mA] 800 720 480 304<br />
Remote Voltage Programming (16 bit) (750/1500 W)<br />
Resolution (0.012 % of Vo Rated) [mV] 0.72 0.96 1.50 2.40<br />
Accuracy (0.05 % Vo Rated + 0.05 % of Vo Actual Output) [mV] 6.0 8.0 12.5 20<br />
Readback Voltage (750/1500 W)<br />
Resolution (0.012 % of Vo Rated) [mV] 0.72 0.96 1.50 2.40<br />
Accuracy (0.1 % Vo Rated + 0.1 % of Vo Actual Output) [mV] 12 16 25 40<br />
OVP/UVL Programming (750 W/1500 W)<br />
Resolution (0.1 % of Vo Rated) [mV] 6 8 12 20<br />
Accuracy (1 % of Vo Rated) [mV] 60 80 125 200<br />
Analog Programming and Monitoring (750 W/1500 W)<br />
Vout Voltage Programming<br />
Iout Voltage Programming<br />
Vout Resistor Programming<br />
Iout Resistor Programming<br />
On/Off control (rear panel)<br />
Output current monitor<br />
Output voltage monitor<br />
Power supply OK signal<br />
CV/CC indicator<br />
Enable/Disable<br />
Local/Remote analog control<br />
Local/Remote analog control indicator<br />
0~100 %, 0~5 V or 0~10 V, user-selectable.<br />
Accuracy and linearity: ± 0.5 % of rated Vout.<br />
0~100 %, 0~5 V or 0~10 V, user-selectable.<br />
Accuracy and linearity: ± 1 % of rated lout.<br />
0~100 %, 0~5/10 kΩ full scale, user-selectable.<br />
Accuracy and linearity: ± 1 % of rated Vout.<br />
0~100 %, 0~5/10 kΩ full scale, user-selectable.<br />
Accuracy and linearity: ± 1.5 % of rated lout.<br />
By electrical. Voltage: 0~0.6 V/2~15 V, or dry contact,<br />
user-selectable logic<br />
0~5 V or 0~10 V, accuracy: 1 %, user-selectable<br />
0~5 V or 0~10 V, accuracy: 1 %, user-selectable<br />
TTL high (4~5 V) -OK, 0 V-Fail 500 series resistance<br />
CV: TTL high (4~5 V), CC: TTL low (0~0.6 V),<br />
maximum Voltage: 30 V, sink current: 10 mA<br />
Dry contact. Open: off, Short: on. Max. voltage at<br />
Enable/Disable in: 6 V<br />
By electrical signal (TTL) or Open/Short: 0~0.6 V or short:<br />
Remote, 4~5 V or open: Local<br />
Open collector, Local: Open, Remote: On. Maximum voltage:<br />
30 V, maximum sink current: 5 mA<br />
34