Chapter 4: <strong>Water</strong> Distribution<br />

detention time, thereby promoting water quality. Single supplies will be considered in<br />

need of reinforcement when serving 40 homes or 4 commercial establishments.<br />

b. The maximum length of permanent dead-end water pipes is 500 feet. Where possible,<br />

water pipes shall be looped to eliminate dead ends, promote better water quality, and<br />

increase fire protection.<br />

2. The maximum curvature by joint deflection for water pipes equal to or less than 12-inch<br />

diameter is a 300 foot radius arc (3.5 degrees/joint with 18 foot pipe sections). For pipes<br />

larger than 12 inches, the maximum curvature by deflection is a 500 foot radius arc.<br />

When restrained joint pipe is specified, consult manufactures recommendations for<br />

maximum joint deflection.<br />

3. Fittings and blockings should not be placed atop other utilities to avoid placement in<br />

disturbed ground.<br />

4. <strong>Water</strong> pipes (and associated land disturbance) shall be located outside of very steep slope<br />

areas in accordance with Section 5-1508 and other pertinent sections of the <strong>Loudoun</strong><br />

County Zoning Ordinance.<br />

5. Any relocation of existing water facilities due to development is the responsibility of the<br />

Developer. Where grading is to occur, resulting cover on existing water pipe must remain<br />

above design minimum and may be considered excessive if adding more than 4 feet.<br />

Encumbrance of pipes for future access and/or re-excavation will necessitate replacement<br />

in kind, in the form of a parallel facility.<br />

6. Separation<br />

a. Provide a minimum 10 foot horizontal separation (outside to outside) with sanitary<br />

sewers, including manholes.<br />

b. Provide a minimum 6 foot horizontal separation (outside to outside) with storm<br />

drainage structures.<br />

c. Provide a minimum 15 foot horizontal separation to a building or other above-ground<br />

structure.<br />

7. Street <strong>Design</strong><br />

a. In public right of way, placement must be in accordance with current requirements of<br />

the Virginia Department of Transportation.<br />

b. Along divided roads water pipes will be located outside the ultimate right-of-way.<br />

c. Along undivided roads, water pipes will be allowed under the pavement, a minimum 5<br />

feet from the outside edge of pavement or gutter pan (7 feet from the face of standard<br />

curb and gutter). Where the pavement width is 24 feet or less, 3 foot horizontal<br />

separation from the gutter pan is permitted, if needed to attain separation from sanitary<br />

sewer. Generally centerline of water pipe should be located 8 feet off the centerline of<br />

<strong>Engineering</strong> <strong>Design</strong> <strong>Manual</strong><br />

September 2010 35