LEGEND HEATERS<br />
SERVICE WORKBOOK<br />
VENTING OPTIONS<br />
Outside air intake and exhaust terminations should be located so exhausted flue gas<br />
moisture will not condense and freeze over the air intake or cause a nuisance or hazard<br />
to pedestrians or the equipment. (Ref: NFPA 54, ANSI Z223. 1, for complete Guidelines).<br />
LEGEND HEATERS<br />
SERVICE WORKBOOK<br />
TABLE 1 PERIODIC TESTING RECOMMENDATIONS FOR IRI<br />
EQUIPPED MODELS<br />
Item Frequency Accomplished By Remarks<br />
1. Gages and Indicators Daily Operator Visually inspect, log<br />
observations<br />
2. Burner Flame Daily Operator Visually inspect for<br />
uniform blue flames<br />
3. Flame Signal Strength Weekly Operator Check flame signal<br />
strength with meter<br />
and log<br />
4. Flame Failure Detection Weekly Operator Close Manual<br />
Shutoff Valve,<br />
check safety<br />
shutdown time, log<br />
5. Gas Valves Weekly Operator Open Operating<br />
Control, listen for<br />
valve closure,<br />
check for voltage<br />
6. Flow Switch/ Low <strong>Water</strong><br />
cutoff<br />
Weekly Operator See detailed<br />
instructions<br />
7. Vent System Monthly Operator See Operating<br />
Manual<br />
8. Condensate Drains Monthly Operator See Operating<br />
Manual<br />
9. Blocked flue and blower Monthly Operator See detailed<br />
instructions<br />
10. Gas pressure switches Monthly Operator See detailed<br />
instructions<br />
11. Burner components Semiannually Service Technician See detailed<br />
instructions<br />
12. Transformer Semiannually Service Technician Check primary &<br />
secondary voltage,<br />
log<br />
13. High Limit and<br />
Operating Control<br />
Annually Service Technician See detailed<br />
instructions<br />
14. Safety Valves As Required Operator See detailed<br />
15. Drip Leg and gas<br />
strainer<br />
instructions<br />
As Required Operator See detailed<br />
instructions<br />
Direct Venting: Maximum 60 equivalent feet exhaust and 60 equivalent feet intake air<br />
vent.<br />
IRI Equipped Models – Cont.<br />
A.O. <strong>Smith</strong> <strong>Water</strong> Products Co.<br />
Irving, Texas © 1997<br />
15<br />
Service Workbook<br />
Training Department<br />
A.O. <strong>Smith</strong> <strong>Water</strong> Products Co.<br />
Irving, Texas © 1997<br />
65<br />
Service Workbook<br />
Training Department