LEGEND HEATERS<br />

SERVICE WORKBOOK<br />

VENTING OPTIONS<br />

Outside air intake and exhaust terminations should be located so exhausted flue gas<br />

moisture will not condense and freeze over the air intake or cause a nuisance or hazard<br />

to pedestrians or the equipment. (Ref: NFPA 54, ANSI Z223. 1, for complete Guidelines).<br />

LEGEND HEATERS<br />

SERVICE WORKBOOK<br />

TABLE 1 PERIODIC TESTING RECOMMENDATIONS FOR IRI<br />

EQUIPPED MODELS<br />

Item Frequency Accomplished By Remarks<br />

1. Gages and Indicators Daily Operator Visually inspect, log<br />

observations<br />

2. Burner Flame Daily Operator Visually inspect for<br />

uniform blue flames<br />

3. Flame Signal Strength Weekly Operator Check flame signal<br />

strength with meter<br />

and log<br />

4. Flame Failure Detection Weekly Operator Close Manual<br />

Shutoff Valve,<br />

check safety<br />

shutdown time, log<br />

5. Gas Valves Weekly Operator Open Operating<br />

Control, listen for<br />

valve closure,<br />

check for voltage<br />

6. Flow Switch/ Low <strong>Water</strong><br />

cutoff<br />

Weekly Operator See detailed<br />

instructions<br />

7. Vent System Monthly Operator See Operating<br />

Manual<br />

8. Condensate Drains Monthly Operator See Operating<br />

Manual<br />

9. Blocked flue and blower Monthly Operator See detailed<br />

instructions<br />

10. Gas pressure switches Monthly Operator See detailed<br />

instructions<br />

11. Burner components Semiannually Service Technician See detailed<br />

instructions<br />

12. Transformer Semiannually Service Technician Check primary &<br />

secondary voltage,<br />

log<br />

13. High Limit and<br />

Operating Control<br />

Annually Service Technician See detailed<br />

instructions<br />

14. Safety Valves As Required Operator See detailed<br />

15. Drip Leg and gas<br />

strainer<br />

instructions<br />

As Required Operator See detailed<br />

instructions<br />

Direct Venting: Maximum 60 equivalent feet exhaust and 60 equivalent feet intake air<br />

vent.<br />

IRI Equipped Models – Cont.<br />

A.O. <strong>Smith</strong> <strong>Water</strong> Products Co.<br />

Irving, Texas © 1997<br />

15<br />

Service Workbook<br />

Training Department<br />

A.O. <strong>Smith</strong> <strong>Water</strong> Products Co.<br />

Irving, Texas © 1997<br />

65<br />

Service Workbook<br />

Training Department