25.01.2015 Views

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MEDIUM VOLTAGE CABLES<br />

12 / 20 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 12 / 20 (24) kV<br />

Impulse test voltage (peak value) 125 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 42 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

35 6.90 0.3 5.5 0.3 0.076 2.50 57.9 5648 500<br />

50 8.10 0.3 5.5 0.3 0.076 2.50 60.9 6344 500<br />

70 9.70 0.3 5.5 0.3 0.076 2.50 64.6 7323 500<br />

95 11.30 0.3 5.5 0.3 0.076 2.50 68.4 8461 500<br />

120 12.60 0.3 5.5 0.3 0.076 3.15 73.7 10562 500<br />

150 14.10 0.3 5.5 0.3 0.076 3.15 77.2 11722 500<br />

185 15.80 0.3 5.5 0.3 0.076 3.15 81.3 13320 500<br />

240 18.10 0.3 5.5 0.3 0.076 3.15 86.8 15664 400<br />

300 20.50 0.3 5.5 0.3 0.076 3.15 92.4 18139 350<br />

400 23.10 0.3 5.5 0.3 0.076 3.15 98.8 21409 300<br />

Cable Code<br />

C317XK3BBWMRDXXI0MF<br />

C318XK3BBWMRDXXI0MF<br />

C319XK3BBWMRDXXI0MF<br />

C345XK3BBWMRDXXI0MF<br />

C346XK3BBWMRDXXI0MF<br />

C347XK3BBWMRDXXI0MF<br />

C348XK3BBWMRDXXI0MF<br />

C349XK3BBWMRDXXI0MU<br />

C350XK3BBWMRDXXI0MV<br />

C351XK3BBWMRDXXI0MT<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

35 0.5240 0.6684 0.161 0.687 0.159<br />

146<br />

126<br />

163<br />

50 0.3870 0.4939 0.149 0.516 0.175<br />

171<br />

149<br />

193<br />

70 0.2680 0.3423 0.141 0.370 0.196<br />

208<br />

182<br />

238<br />

95 0.1930 0.2470 0.134 0.281 0.217<br />

247<br />

217<br />

287<br />

120 0.1530 0.1963 0.130 0.235 0.234<br />

278<br />

245<br />

327<br />

150 0.1240 0.1597 0.126 0.203 0.254<br />

309<br />

274<br />

369<br />

185 0.0991 0.1285 0.121 0.176 0.276<br />

345<br />

307<br />

417<br />

240 0.0754 0.0991 0.116 0.153 0.305<br />

391<br />

351<br />

482<br />

300 0.0601 0.0805 0.112 0.138 0.336<br />

431<br />

389<br />

541<br />

400 0.0470 0.0650 0.108 0.126 0.369<br />

475<br />

431<br />

606<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)