MEDIUM VOLTAGE CABLES<br />
8.7 / 15 kV<br />
TECHNICAL DATA<br />
Rated voltage U o / U (U m ) 8.7 / 15 (17.5) kV<br />
Impulse test voltage (peak value) 95 kV<br />
<strong>Power</strong> frequency test voltage for 5 minutes 30.5 kV<br />
Max. conductor operating temperature at Normal conditions 90 °C<br />
Max. conductor operating temperature at Emergency conditions 130 °C<br />
Max. conductor operating temperature at Short circuit conditions 250 °C<br />
Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />
Constructional Data<br />
Nominal<br />
area of<br />
conductor<br />
Conductor<br />
Approx.<br />
conductor<br />
diameter<br />
Insulation Screen Armour Packing<br />
Thickness of insulation layers<br />
C.S XLPE I.S<br />
Min. Nom. Min.<br />
Approx.<br />
metallic<br />
screen tape<br />
thickness<br />
Tape<br />
thickness<br />
Approx.<br />
overall<br />
diameter<br />
Approx.<br />
overall<br />
weight<br />
Standard<br />
cutting<br />
length<br />
± 5 %<br />
mm 2 mm mm mm mm mm mm mm kg / km m<br />
25 5.85 0.3 4.5 0.3 0.076 0.50 47.5 2612 1000<br />
35 6.90 0.3 4.5 0.3 0.076 0.50 49.8 2865 1000<br />
50 8.10 0.3 4.5 0.3 0.076 0.50 52.8 3217 1000<br />
70 9.70 0.3 4.5 0.3 0.076 0.50 56.5 3678 1000<br />
95 11.30 0.3 4.5 0.3 0.076 0.50 60.5 4233 500<br />
120 12.60 0.3 4.5 0.3 0.076 0.50 63.7 4734 500<br />
150 14.10 0.3 4.5 0.3 0.076 0.50 67.2 5249 500<br />
185 15.80 0.3 4.5 0.3 0.076 0.50 71.2 5922 500<br />
240 18.10 0.3 4.5 0.3 0.076 0.50 76.8 6927 500<br />
300 20.50 0.3 4.5 0.3 0.076 0.80 83.8 8766 400<br />
400 23.10 0.3 4.5 0.3 0.076 0.80 90.0 10157 350<br />
Cable Code<br />
A316XJ3BBGMRDXXI0MR<br />
A317XJ3BBGMRDXXI0MR<br />
A318XJ3BBGMRDXXI0MR<br />
A319XJ3BBGMRDXXI0MR<br />
A345XJ3BBGMRDXXI0MF<br />
A346XJ3BBGMRDXXI0MF<br />
A347XJ3BBGMRDXXI0MF<br />
A348XJ3BBGMRDXXI0MF<br />
A349XJ3BBGMRDXXI0MF<br />
A350XJ3BBGMRDXXI0MU<br />
A351XJ3BBGMRDXXI0MV<br />
Electrical Data<br />
Nominal<br />
area<br />
of<br />
conductor<br />
Electrical Characteristics<br />
Max. Conductor<br />
Resistance<br />
Reactance<br />
(60 Hz)<br />
DC at<br />
20 °C<br />
AC at<br />
90 °C<br />
Impedance<br />
(90 °C,<br />
60 Hz)<br />
Capacitance<br />
Buried direct<br />
in the ground<br />
Continuous Current Ratings<br />
In a buried duct<br />
In air<br />
Fig. (a) Fig. (b) Fig. (c)<br />
mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />
25 1.2000 1.5386 0.161 1.547 0.166<br />
95<br />
81<br />
103<br />
35 0.8680 1.1130 0.153 1.123 0.183<br />
113<br />
97<br />
124<br />
50 0.6410 0.8221 0.142 0.834 0.202<br />
133<br />
114<br />
147<br />
70 0.4430 0.5684 0.134 0.584 0.228<br />
162<br />
140<br />
183<br />
95 0.3200 0.4109 0.128 0.430 0.253<br />
192<br />
168<br />
221<br />
120 0.2530 0.3252 0.124 0.348 0.273<br />
218<br />
191<br />
253<br />
150 0.2060 0.2652 0.120 0.291 0.297<br />
244<br />
215<br />
287<br />
185 0.1640 0.2117 0.115 0.241 0.324<br />
275<br />
244<br />
328<br />
240 0.1250 0.1622 0.111 0.197 0.360<br />
318<br />
284<br />
385<br />
300 0.1000 0.1308 0.107 0.169 0.397<br />
357<br />
321<br />
439<br />
400 0.0778 0.1032 0.104 0.146 0.438<br />
406<br />
368<br />
508<br />
Fig. (a)<br />
Fig. (b)<br />
0.3 x De<br />
Fig. (c)