Annex E: Derating Factors<br />
<strong>Cables</strong> on horizontal perforated trays (spaced)<br />
Clearance = 2 cable diameter (D e )<br />
Clearance from the wall ≥ 20 mm<br />
Number of trays<br />
Number of three-phase circuits<br />
1 2 3<br />
Laying form<br />
1<br />
2<br />
3<br />
1.00<br />
0.97<br />
0.96<br />
0.98<br />
0.93<br />
0.92<br />
0.96<br />
0.89<br />
0.86<br />
2D<br />
20 mm<br />
e<br />
D<br />
e<br />
<strong>Cables</strong> on vertical perforated trays (spaced)<br />
Laying form<br />
Clearance = 2 cable diameter (D e )<br />
Clearance betw. trays ≥ 225 mm<br />
Number of three-phase circuits<br />
Number of trays<br />
1<br />
1 2 3<br />
1.00<br />
0.91<br />
0.89<br />
225 mm<br />
2D e<br />
2<br />
1.00<br />
0.90<br />
0.86<br />
D e<br />
3<br />
-<br />
-<br />
-<br />
<strong>Cables</strong> on ladder supported, cleats, etc. (spaced)<br />
Clearance = 2 cable diameter (D e )<br />
Clearance from the wall ≥ 20 mm<br />
Number of trays<br />
Number of three-phase circuits<br />
1 2 3<br />
Laying form<br />
1<br />
1.00<br />
1.00<br />
1.00<br />
2D<br />
e<br />
D<br />
e<br />
2<br />
3<br />
0.97<br />
0.96<br />
0.95<br />
0.94<br />
0.93<br />
0.90<br />
20 mm<br />
NOTES:<br />
1 . Values given have to be applied to the current carrying capacity for one three-phase circuit of single-core<br />
cables in free air, either in trefoil or horizontal (flat) formation.<br />
2 . Values given are averages for the cable types and range of conductor sizes considered. The spread of values is<br />
generally less than 5 %.<br />
3 . Factors are given for single layer of cables (or trefoil groups) as shown in the table and do not apply when<br />
cables are installed in more than one layer touching each other. Values for such installations may be significantly<br />
lower and should be determined by an appropriate method.<br />
4 . Values are given for vertical spacing between trays of 300 mm. For closer spacing, the factors should be reduced.<br />
5 . Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer<br />
spacing, the factors should be reduced.<br />
6 . For circuits having more than one cable in parallel per phase, each three phase set of conductors should be<br />
considered as a circuit for the purpose of this table.<br />
153