Annex E: Derating Factors<br />

<strong>Cables</strong> on horizontal perforated trays (spaced)<br />

Clearance = 2 cable diameter (D e )<br />

Clearance from the wall ≥ 20 mm<br />

Number of trays<br />

Number of three-phase circuits<br />

1 2 3<br />

Laying form<br />

1<br />

2<br />

3<br />

1.00<br />

0.97<br />

0.96<br />

0.98<br />

0.93<br />

0.92<br />

0.96<br />

0.89<br />

0.86<br />

2D<br />

20 mm<br />

e<br />

D<br />

e<br />

<strong>Cables</strong> on vertical perforated trays (spaced)<br />

Laying form<br />

Clearance = 2 cable diameter (D e )<br />

Clearance betw. trays ≥ 225 mm<br />

Number of three-phase circuits<br />

Number of trays<br />

1<br />

1 2 3<br />

1.00<br />

0.91<br />

0.89<br />

225 mm<br />

2D e<br />

2<br />

1.00<br />

0.90<br />

0.86<br />

D e<br />

3<br />

-<br />

-<br />

-<br />

<strong>Cables</strong> on ladder supported, cleats, etc. (spaced)<br />

Clearance = 2 cable diameter (D e )<br />

Clearance from the wall ≥ 20 mm<br />

Number of trays<br />

Number of three-phase circuits<br />

1 2 3<br />

Laying form<br />

1<br />

1.00<br />

1.00<br />

1.00<br />

2D<br />

e<br />

D<br />

e<br />

2<br />

3<br />

0.97<br />

0.96<br />

0.95<br />

0.94<br />

0.93<br />

0.90<br />

20 mm<br />

NOTES:<br />

1 . Values given have to be applied to the current carrying capacity for one three-phase circuit of single-core<br />

cables in free air, either in trefoil or horizontal (flat) formation.<br />

2 . Values given are averages for the cable types and range of conductor sizes considered. The spread of values is<br />

generally less than 5 %.<br />

3 . Factors are given for single layer of cables (or trefoil groups) as shown in the table and do not apply when<br />

cables are installed in more than one layer touching each other. Values for such installations may be significantly<br />

lower and should be determined by an appropriate method.<br />

4 . Values are given for vertical spacing between trays of 300 mm. For closer spacing, the factors should be reduced.<br />

5 . Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer<br />

spacing, the factors should be reduced.<br />

6 . For circuits having more than one cable in parallel per phase, each three phase set of conductors should be<br />

considered as a circuit for the purpose of this table.<br />

153