MEDIUM VOLTAGE CABLES<br />

3.6 / 6 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 3.6 / 6 (7.2) kV<br />

Impulse test voltage (peak value) 60 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 12.5 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

25 5.85 0.3 2.5 0.3 0.076 2.00 40.0 3079 1000<br />

35 6.90 0.3 2.5 0.3 0.076 2.50 43.6 3952 1000<br />

50 8.10 0.3 2.5 0.3 0.076 2.50 46.4 4560 1000<br />

70 9.70 0.3 2.5 0.3 0.076 2.50 50.2 5479 1000<br />

95 11.30 0.3 2.5 0.3 0.076 2.50 53.9 6521 500<br />

120 12.60 0.3 2.5 0.3 0.076 2.50 57.3 7554 500<br />

150 14.10 0.3 2.5 0.3 0.076 2.50 60.9 8626 500<br />

185 15.80 0.3 2.5 0.3 0.076 2.50 64.8 10069 500<br />

240 18.10 0.3 2.6 0.3 0.076 2.50 70.8 12287 500<br />

300 20.50 0.3 2.8 0.3 0.076 3.15 79.3 15768 400<br />

400 23.10 0.3 3.0 0.3 0.076 3.15 86.8 19124 350<br />

Cable Code<br />

C316XF3BBWMRDXXI0MR<br />

C317XF3BBWMRDXXI0MR<br />

C318XF3BBWMRDXXI0MR<br />

C319XF3BBWMRDXXI0MR<br />

C345XF3BBWMRDXXI0MF<br />

C346XF3BBWMRDXXI0MF<br />

C347XF3BBWMRDXXI0MF<br />

C348XF3BBWMRDXXI0MF<br />

C349XF3BBWMRDXXI0MF<br />

C350XF3BBWMRDXXI0MU<br />

C351XF3BBWMRDXXI0MV<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

25 0.7270 0.9272 0.141 0.938 0.255<br />

123<br />

106<br />

135<br />

35 0.5240 0.6685 0.133 0.682 0.283<br />

146<br />

126<br />

163<br />

50 0.3870 0.4940 0.124 0.509 0.317<br />

171<br />

149<br />

193<br />

70 0.2680 0.3426 0.118 0.362 0.362<br />

208<br />

182<br />

238<br />

95 0.1930 0.2474 0.113 0.272 0.407<br />

247<br />

217<br />

287<br />

120 0.1530 0.1968 0.110 0.225 0.444<br />

278<br />

245<br />

327<br />

150 0.1240 0.1603 0.107 0.193 0.486<br />

309<br />

274<br />

369<br />

185 0.0991 0.1292 0.103 0.165 0.533<br />

345<br />

307<br />

417<br />

240 0.0754 0.1000 0.100 0.142 0.577<br />

391<br />

351<br />

482<br />

300 0.0601 0.0815 0.099 0.128 0.600<br />

431<br />

389<br />

541<br />

400 0.0470 0.0661 0.097 0.117 0.625<br />

475<br />

431<br />

606<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)