25.01.2015 Views

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MEDIUM VOLTAGE CABLES<br />

18 / 30 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 18 / 30 (36) kV<br />

Impulse test voltage (peak value) 170 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 63 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

50 8.10 0.3 8.0 0.3 0.076 3.15 74.8 9045 500<br />

70 9.70 0.3 8.0 0.3 0.076 3.15 78.5 10125 500<br />

95 11.30 0.3 8.0 0.3 0.076 3.15 82.5 11412 500<br />

120 12.60 0.3 8.0 0.3 0.076 3.15 85.7 12622 500<br />

150 14.10 0.3 8.0 0.3 0.076 3.15 89.2 13840 400<br />

185 15.80 0.3 8.0 0.3 0.076 3.15 93.3 15508 400<br />

240 18.10 0.3 8.0 0.3 0.076 3.15 98.8 17949 400<br />

300 20.50 0.3 8.0 0.3 0.076 3.15 104.4 20520 300<br />

400 23.10 0.3 8.0 0.3 0.076 3.15 110.8 23905 300<br />

Cable Code<br />

C318XM3BBWMRDXXI0MF<br />

C319XM3BBWMRDXXI0MF<br />

C345XM3BBWMRDXXI0MF<br />

C346XM3BBWMRDXXI0MF<br />

C347XM3BBWMRDXXI0MU<br />

C348XM3BBWMRDXXI0MU<br />

C349XM3BBWMRDXXI0MU<br />

C350XM3BBWMRDXXI0MT<br />

C351XM3BBWMRDXXI0MT<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

50 0.3870 0.4938 0.165 0.521 0.137<br />

171<br />

149<br />

193<br />

70 0.2680 0.3423 0.156 0.376 0.152<br />

208<br />

182<br />

238<br />

95 0.1930 0.2469 0.149 0.288 0.167<br />

247<br />

217<br />

287<br />

120 0.1530 0.1961 0.144 0.243 0.179<br />

278<br />

245<br />

327<br />

150 0.1240 0.1595 0.139 0.211 0.192<br />

309<br />

274<br />

369<br />

185 0.0991 0.1282 0.133 0.185 0.208<br />

345<br />

307<br />

417<br />

240 0.0754 0.0986 0.127 0.161 0.228<br />

391<br />

351<br />

482<br />

300 0.0601 0.0799 0.123 0.146 0.250<br />

431<br />

389<br />

541<br />

400 0.0470 0.0643 0.118 0.134 0.273<br />

475<br />

431<br />

606<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!