Single-Core <strong>Cables</strong>, with Copper Conductors, XLPE Insulated,<br />

Tape Armoured and PVC Sheathed<br />

APPLICATION<br />

Suitable for installations indoors: mostly in power supply stations and outdoors: in cable ducts, underground, and on cable<br />

trays for industries, switch-boards and power stations. Due to the good laying and mechanical characteristics, this cable<br />

is suitable when mechanical protection is required or in applications where mechanical damages are expected to occur.<br />

APPLICABLE STANDARDS<br />

medium voltage cables are designed and tested to meet or exceed the requirements of IEC 60502-2 standard.<br />

However, can also supply a range of alternative designs to meet customer-specified requirements.<br />

CABLE CONSTRUCTION<br />

Conductor<br />

Plain annealed stranded circular compacted copper conductor (Class 2).<br />

Conductor Screen<br />

Extruded layer of a cross-linkable semi-conducting compound<br />

as a stress control layer.<br />

Insulation<br />

Extruded layer of cross-linked polyethylene (XLPE).<br />

Insulation Screen<br />

Extruded layer of a cross-linkable semi-conducting<br />

compound firmly bonded to the insulation.<br />

Metallic Screen<br />

Flat plain copper tape helically applied over the insulation<br />

screen with suitable overlap.<br />

Bedding<br />

Extruded layer of Polyvinyl chloride (PVC).<br />

Conductor<br />

Conductor Screen<br />

XLPE Insulation<br />

Insulation Screen<br />

Metallic Screen<br />

Bedding<br />

Tape Armouring<br />

Outer Jacket<br />

Armouring<br />

Double layer of non-magnetic (aluminum) tapes.<br />

Outer Jacket<br />

Extruded layer of Polyvinyl chloride (PVC).<br />

Note: The conductor screen, XLPE insulation and the insulation screen are extruded simultaneously in one process using triple extrusion method<br />

(Continuous Vulcanization Line). Triple extrusion method not only assures clean interfaces between the insulation and stress control layers, but also<br />

assures a construction free of Partial Discharge with high operational reliability.<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 6 / 10 (12) kV<br />

Impulse test voltage (peak value) 75 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 15 Ø<br />

41<br />

The above data is approximate and subject to manufacturing tolerance.<br />

We reserve the right to change the above figures as a result of product development and/or changes in standard.