MEDIUM VOLTAGE CABLES<br />

12 / 20 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 12 / 20 (24) kV<br />

Impulse test voltage (peak value) 125 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 42 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Tape<br />

thickness<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

35 6.90 0.3 5.5 0.3 0.076 0.50 54.7 3979 500<br />

50 8.10 0.3 5.5 0.3 0.076 0.50 57.7 4589 500<br />

70 9.70 0.3 5.5 0.3 0.076 0.50 61.4 5452 500<br />

95 11.30 0.3 5.5 0.3 0.076 0.50 65.2 6475 500<br />

120 12.60 0.3 5.5 0.3 0.076 0.50 68.4 7466 500<br />

150 14.10 0.3 5.5 0.3 0.076 0.50 71.9 8468 500<br />

185 15.80 0.3 5.5 0.3 0.076 0.50 76.2 9951 500<br />

240 18.10 0.3 5.5 0.3 0.076 0.80 82.9 12791 500<br />

300 20.50 0.3 5.5 0.3 0.076 0.80 88.5 15060 400<br />

400 23.10 0.3 5.5 0.3 0.076 0.80 94.9 18128 350<br />

Cable Code<br />

C317XK3BBGMRDXXI0MF<br />

C318XK3BBGMRDXXI0MF<br />

C319XK3BBGMRDXXI0MF<br />

C345XK3BBGMRDXXI0MF<br />

C346XK3BBGMRDXXI0MF<br />

C347XK3BBGMRDXXI0MF<br />

C348XK3BBGMRDXXI0MF<br />

C349XK3BBGMRDXXI0MF<br />

C350XK3BBGMRDXXI0MU<br />

C351XK3BBGMRDXXI0MV<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

35 0.5240 0.6684 0.161 0.687 0.159<br />

146<br />

125<br />

160<br />

50 0.3870 0.4939 0.149 0.516 0.175<br />

171<br />

147<br />

190<br />

70 0.2680 0.3423 0.141 0.370 0.196<br />

208<br />

180<br />

235<br />

95 0.1930 0.2470 0.134 0.281 0.217<br />

248<br />

216<br />

285<br />

120 0.1530 0.1963 0.130 0.235 0.234<br />

280<br />

245<br />

325<br />

150 0.1240 0.1597 0.126 0.203 0.254<br />

313<br />

276<br />

369<br />

185 0.0991 0.1285 0.121 0.176 0.276<br />

352<br />

312<br />

419<br />

240 0.0754 0.0991 0.116 0.153 0.305<br />

404<br />

360<br />

489<br />

300 0.0601 0.0805 0.112 0.138 0.336<br />

451<br />

405<br />

555<br />

400 0.0470 0.0650 0.108 0.126 0.369<br />

506<br />

458<br />

633<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)