Table E.12<br />

Derating factors for groups of three-phase circuits of single-core cables in single-way ducts<br />

Number of cables<br />

in group<br />

Spacing between group centers<br />

Touching 200 mm 400 mm 600 mm 800 mm<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

0.78<br />

0.66<br />

0.59<br />

0.55<br />

0.51<br />

0.48<br />

0.46<br />

0.44<br />

0.43<br />

0.42<br />

0.40<br />

0.85<br />

0.75<br />

0.70<br />

0.66<br />

0.64<br />

0.61<br />

0.60<br />

0.58<br />

0.57<br />

0.56<br />

0.55<br />

0.89<br />

0.81<br />

0.77<br />

0.74<br />

0.72<br />

0.71<br />

0.70<br />

0.69<br />

0.68<br />

0.67<br />

0.67<br />

0.91<br />

0.85<br />

0.82<br />

0.80<br />

0.78<br />

0.77<br />

0.76<br />

0.76<br />

-<br />

-<br />

-<br />

0.93<br />

0.88<br />

0.86<br />

0.84<br />

0.83<br />

0.82<br />

-<br />

-<br />

-<br />

-<br />

-<br />

Table E.13<br />

Derating factors for groups of more than one three-core cable in air<br />

<strong>Cables</strong> on horizontal perforated trays (touching)<br />

Clearance from the wall ≥ 20 mm<br />

Number of trays<br />

Number of cables (three-phase circuits)<br />

1 2 3 4 6 9<br />

Laying form<br />

1<br />

1.00<br />

0.88<br />

0.82<br />

0.79<br />

0.76<br />

0.73<br />

2<br />

1.00<br />

0.87<br />

0.80<br />

0.77<br />

0.73<br />

0.68<br />

3<br />

1.00<br />

0.86<br />

0.79<br />

0.76<br />

0.71<br />

0.66<br />

20 mm<br />

<strong>Cables</strong> on horizontal perforated trays (spaced)<br />

Clearance = cable diameter (D e )<br />

Clearance from the wall ≥ 20 mm<br />

Number of trays<br />

Number of cables (three-phase circuits)<br />

1 2 3 4 6 9<br />

Laying form<br />

1<br />

1.00<br />

1.00<br />

0.98<br />

0.95<br />

0.91<br />

-<br />

D e<br />

2<br />

1.00<br />

0.99<br />

0.96<br />

0.92<br />

0.87<br />

-<br />

3<br />

1.00<br />

0.98<br />

0.95<br />

0.91<br />

0.85<br />

-<br />

20 mm