MEDIUM VOLTAGE CABLES<br />

6 / 10 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 6 / 10 (12) kV<br />

Impulse test voltage (peak value) 75 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

25 5.85 0.3 3.4 0.3 0.076 2.50 45.5 3471 1000<br />

35 6.90 0.3 3.4 0.3 0.076 2.50 47.9 3769 1000<br />

50 8.10 0.3 3.4 0.3 0.076 2.50 50.9 4220 1000<br />

70 9.70 0.3 3.4 0.3 0.076 2.50 54.7 4790 1000<br />

95 11.30 0.3 3.4 0.3 0.076 2.50 58.4 5381 500<br />

120 12.60 0.3 3.4 0.3 0.076 2.50 61.6 5942 500<br />

150 14.10 0.3 3.4 0.3 0.076 2.50 65.0 6540 500<br />

185 15.80 0.3 3.4 0.3 0.076 2.50 69.1 7303 500<br />

240 18.10 0.3 3.4 0.3 0.076 3.15 76.6 9403 500<br />

300 20.50 0.3 3.4 0.3 0.076 3.15 82.3 10682 500<br />

400 23.10 0.3 3.4 0.3 0.076 3.15 88.6 12231 400<br />

Cable Code<br />

A316XH3BBWMRDXXI0MR<br />

A317XH3BBWMRDXXI0MR<br />

A318XH3BBWMRDXXI0MR<br />

A319XH3BBWMRDXXI0MR<br />

A345XH3BBWMRDXXI0MF<br />

A346XH3BBWMRDXXI0MF<br />

A347XH3BBWMRDXXI0MF<br />

A348XH3BBWMRDXXI0MF<br />

A349XH3BBWMRDXXI0MF<br />

A350XH3BBWMRDXXI0MF<br />

A351XH3BBWMRDXXI0MU<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

25 1.2000 1.5386 0.150 1.546 0.202<br />

96<br />

82<br />

105<br />

35 0.8680 1.1131 0.143 0.122 0.224<br />

114<br />

98<br />

126<br />

50 0.6410 0.8221 0.133 0.833 0.249<br />

133<br />

116<br />

150<br />

70 0.4430 0.5684 0.126 0.582 0.282<br />

162<br />

142<br />

185<br />

95 0.3200 0.4110 0.120 0.428 0.316<br />

193<br />

169<br />

224<br />

120 0.2530 0.3253 0.116 0.345 0.343<br />

217<br />

192<br />

256<br />

150 0.2060 0.2653 0.113 0.288 0.374<br />

243<br />

215<br />

289<br />

185 0.1640 0.2118 0.109 0.238 0.409<br />

273<br />

243<br />

329<br />

240 0.1250 0.1624 0.105 0.193 0.456<br />

312<br />

280<br />

384<br />

300 0.1000 0.1311 0.102 0.166 0.505<br />

348<br />

314<br />

434<br />

400 0.0778 0.1036 0.099 0.143 0.559<br />

390<br />

354<br />

495<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)