25.01.2015 Views

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MEDIUM VOLTAGE CABLES<br />

6 / 10 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 6 / 10 kV<br />

Impulse test voltage (peak value) 75 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

25 5.85 0.3 3.4 0.3 0.076 2.50 45.5 3933 1000<br />

35 6.90 0.3 3.4 0.3 0.076 2.50 47.9 4411 1000<br />

50 8.10 0.3 3.4 0.3 0.076 2.50 50.9 5097 1000<br />

70 9.70 0.3 3.4 0.3 0.076 2.50 54.7 6044 1000<br />

95 11.30 0.3 3.4 0.3 0.076 2.50 58.4 7106 500<br />

120 12.60 0.3 3.4 0.3 0.076 2.50 61.6 8135 500<br />

150 14.10 0.3 3.4 0.3 0.076 2.50 65.0 9198 500<br />

185 15.80 0.3 3.4 0.3 0.076 2.50 69.1 10696 500<br />

240 18.10 0.3 3.4 0.3 0.076 3.15 76.6 13834 500<br />

300 20.50 0.3 3.4 0.3 0.076 3.15 82.3 16262 400<br />

400 23.10 0.3 3.4 0.3 0.076 3.15 88.6 19401 350<br />

Cable Code<br />

C316XH3BBWMRDXXI0MR<br />

C317XH3BBWMRDXXI0MR<br />

C318XH3BBWMRDXXI0MR<br />

C319XH3BBWMRDXXI0MR<br />

C345XH3BBWMRDXXI0MF<br />

C346XH3BBWMRDXXI0MF<br />

C347XH3BBWMRDXXI0MF<br />

C348XH3BBWMRDXXI0MF<br />

C349XH3BBWMRDXXI0MF<br />

C350XH3BBWMRDXXI0MU<br />

C351XH3BBWMRDXXI0MV<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

25 0.7270 0.9272 0.150 0.939 0.202<br />

123<br />

106<br />

135<br />

35 0.5240 0.6685 0.143 0.684 0.224<br />

146<br />

126<br />

163<br />

50 0.3870 0.4939 0.133 0.511 0.249<br />

171<br />

149<br />

193<br />

70 0.2680 0.3425 0.126 0.365 0.282<br />

208<br />

182<br />

238<br />

95 0.1930 0.2472 0.120 0.275 0.316<br />

247<br />

217<br />

287<br />

120 0.1530 0.1966 0.116 0.228 0.343<br />

278<br />

245<br />

327<br />

150 0.1240 0.1601 0.113 0.196 0.374<br />

309<br />

274<br />

369<br />

185 0.0991 0.1289 0.109 0.169 0.409<br />

345<br />

307<br />

417<br />

240 0.0754 0.0997 0.105 0.145 0.456<br />

391<br />

351<br />

482<br />

300 0.0601 0.0812 0.102 0.130 0.505<br />

431<br />

389<br />

541<br />

400 0.0470 0.0659 0.099 0.119 0.559<br />

475<br />

431<br />

606<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!