Medium Voltage Power Cables Catalogue - AEC Online
Medium Voltage Power Cables Catalogue - AEC Online
Medium Voltage Power Cables Catalogue - AEC Online
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
MEDIUM VOLTAGE CABLES<br />
6 / 10 kV<br />
TECHNICAL DATA<br />
Rated voltage U o / U (U m ) 6 / 10 kV<br />
Impulse test voltage (peak value) 75 kV<br />
<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />
Max. conductor operating temperature at Normal conditions 90 °C<br />
Max. conductor operating temperature at Emergency conditions 130 °C<br />
Max. conductor operating temperature at Short circuit conditions 250 °C<br />
Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />
Constructional Data<br />
Nominal<br />
area of<br />
conductor<br />
Conductor<br />
Approx.<br />
conductor<br />
diameter<br />
Insulation Screen Armour Packing<br />
Thickness of insulation layers<br />
C.S XLPE I.S<br />
Min. Nom. Min.<br />
Approx.<br />
metallic<br />
screen tape<br />
thickness<br />
Wire<br />
diameter<br />
Approx.<br />
overall<br />
diameter<br />
Approx.<br />
overall<br />
weight<br />
Standard<br />
cutting<br />
length<br />
± 5 %<br />
mm 2 mm mm mm mm mm mm mm kg / km m<br />
25 5.85 0.3 3.4 0.3 0.076 2.50 45.5 3933 1000<br />
35 6.90 0.3 3.4 0.3 0.076 2.50 47.9 4411 1000<br />
50 8.10 0.3 3.4 0.3 0.076 2.50 50.9 5097 1000<br />
70 9.70 0.3 3.4 0.3 0.076 2.50 54.7 6044 1000<br />
95 11.30 0.3 3.4 0.3 0.076 2.50 58.4 7106 500<br />
120 12.60 0.3 3.4 0.3 0.076 2.50 61.6 8135 500<br />
150 14.10 0.3 3.4 0.3 0.076 2.50 65.0 9198 500<br />
185 15.80 0.3 3.4 0.3 0.076 2.50 69.1 10696 500<br />
240 18.10 0.3 3.4 0.3 0.076 3.15 76.6 13834 500<br />
300 20.50 0.3 3.4 0.3 0.076 3.15 82.3 16262 400<br />
400 23.10 0.3 3.4 0.3 0.076 3.15 88.6 19401 350<br />
Cable Code<br />
C316XH3BBWMRDXXI0MR<br />
C317XH3BBWMRDXXI0MR<br />
C318XH3BBWMRDXXI0MR<br />
C319XH3BBWMRDXXI0MR<br />
C345XH3BBWMRDXXI0MF<br />
C346XH3BBWMRDXXI0MF<br />
C347XH3BBWMRDXXI0MF<br />
C348XH3BBWMRDXXI0MF<br />
C349XH3BBWMRDXXI0MF<br />
C350XH3BBWMRDXXI0MU<br />
C351XH3BBWMRDXXI0MV<br />
Electrical Data<br />
Nominal<br />
area<br />
of<br />
conductor<br />
Electrical Characteristics<br />
Max. Conductor<br />
Resistance<br />
Reactance<br />
(60 Hz)<br />
DC at<br />
20 °C<br />
AC at<br />
90 °C<br />
Impedance<br />
(90 °C,<br />
60 Hz)<br />
Capacitance<br />
Buried direct<br />
in the ground<br />
Continuous Current Ratings<br />
In a buried duct<br />
In air<br />
Fig. (a) Fig. (b) Fig. (c)<br />
mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />
25 0.7270 0.9272 0.150 0.939 0.202<br />
123<br />
106<br />
135<br />
35 0.5240 0.6685 0.143 0.684 0.224<br />
146<br />
126<br />
163<br />
50 0.3870 0.4939 0.133 0.511 0.249<br />
171<br />
149<br />
193<br />
70 0.2680 0.3425 0.126 0.365 0.282<br />
208<br />
182<br />
238<br />
95 0.1930 0.2472 0.120 0.275 0.316<br />
247<br />
217<br />
287<br />
120 0.1530 0.1966 0.116 0.228 0.343<br />
278<br />
245<br />
327<br />
150 0.1240 0.1601 0.113 0.196 0.374<br />
309<br />
274<br />
369<br />
185 0.0991 0.1289 0.109 0.169 0.409<br />
345<br />
307<br />
417<br />
240 0.0754 0.0997 0.105 0.145 0.456<br />
391<br />
351<br />
482<br />
300 0.0601 0.0812 0.102 0.130 0.505<br />
431<br />
389<br />
541<br />
400 0.0470 0.0659 0.099 0.119 0.559<br />
475<br />
431<br />
606<br />
Fig. (a)<br />
Fig. (b)<br />
0.3 x De<br />
Fig. (c)