MEDIUM VOLTAGE CABLES<br />
6 / 10 kV<br />
TECHNICAL DATA<br />
Rated voltage U o / U (U m ) 6 / 10 (12) kV<br />
Impulse test voltage (peak value) 75 kV<br />
<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />
Max. conductor operating temperature at Normal conditions 90 °C<br />
Max. conductor operating temperature at Emergency conditions 130 °C<br />
Max. conductor operating temperature at Short circuit conditions 250 °C<br />
Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />
Constructional Data<br />
Nominal<br />
area of<br />
conductor<br />
Conductor<br />
Approx.<br />
conductor<br />
diameter<br />
Insulation Screen Armour Packing<br />
Thickness of insulation layers<br />
C.S XLPE I.S<br />
Min. Nom. Min.<br />
Approx.<br />
metallic<br />
screen tape<br />
thickness<br />
Tape<br />
thickness<br />
Approx.<br />
overall<br />
diameter<br />
Approx.<br />
overall<br />
weight<br />
Standard<br />
cutting<br />
length<br />
± 5 %<br />
mm 2 mm mm mm mm mm mm mm kg / km m<br />
25 5.85 0.3 3.4 0.3 0.076 0.50 42.3 2176 1000<br />
35 6.90 0.3 3.4 0.3 0.076 0.50 44.5 2398 1000<br />
50 8.10 0.3 3.4 0.3 0.076 0.50 47.7 2749 1000<br />
70 9.70 0.3 3.4 0.3 0.076 0.50 51.5 3204 1000<br />
95 11.30 0.3 3.4 0.3 0.076 0.50 55.2 3679 500<br />
120 12.60 0.3 3.4 0.3 0.076 0.50 58.4 4155 500<br />
150 14.10 0.3 3.4 0.3 0.076 0.50 61.8 4635 500<br />
185 15.80 0.3 3.4 0.3 0.076 0.50 65.9 5286 500<br />
240 18.10 0.3 3.4 0.3 0.076 0.50 71.5 6248 500<br />
300 20.50 0.3 3.4 0.3 0.076 0.50 77.2 7260 500<br />
400 23.10 0.3 3.4 0.3 0.076 0.80 84.7 9333 400<br />
Cable Code<br />
A316XH3BBGMRDXXI0MR<br />
A317XH3BBGMRDXXI0MR<br />
A318XH3BBGMRDXXI0MR<br />
A319XH3BBGMRDXXI0MR<br />
A345XH3BBGMRDXXI0MF<br />
A346XH3BBGMRDXXI0MF<br />
A347XH3BBGMRDXXI0MF<br />
A348XH3BBGMRDXXI0MF<br />
A349XH3BBGMRDXXI0MF<br />
A350XH3BBGMRDXXI0MF<br />
A351XH3BBGMRDXXI0MU<br />
Electrical Data<br />
Nominal<br />
area<br />
of<br />
conductor<br />
Electrical Characteristics<br />
Max. Conductor<br />
Resistance<br />
Reactance<br />
(60 Hz)<br />
DC at<br />
20 °C<br />
AC at<br />
90 °C<br />
Impedance<br />
(90 °C,<br />
60 Hz)<br />
Capacitance<br />
Buried direct<br />
in the ground<br />
Continuous Current Ratings<br />
In a buried duct<br />
In air<br />
Fig. (a) Fig. (b) Fig. (c)<br />
mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />
25 1.2000 1.5386 0.150 1.546 0.202<br />
95<br />
81<br />
103<br />
35 0.8680 1.1131 0.143 0.122 0.224<br />
113<br />
97<br />
124<br />
50 0.6410 0.8221 0.133 0.833 0.249<br />
133<br />
114<br />
147<br />
70 0.4430 0.5684 0.126 0.582 0.282<br />
162<br />
140<br />
183<br />
95 0.3200 0.4110 0.120 0.428 0.316<br />
192<br />
168<br />
221<br />
120 0.2530 0.3253 0.116 0.345 0.343<br />
218<br />
191<br />
253<br />
150 0.2060 0.2653 0.113 0.288 0.374<br />
244<br />
215<br />
287<br />
185 0.1640 0.2118 0.109 0.238 0.409<br />
275<br />
244<br />
328<br />
240 0.1250 0.1624 0.105 0.193 0.456<br />
318<br />
284<br />
385<br />
300 0.1000 0.1311 0.102 0.166 0.505<br />
357<br />
321<br />
439<br />
400 0.0778 0.1036 0.099 0.143 0.559<br />
406<br />
368<br />
508<br />
Fig. (a)<br />
Fig. (b)<br />
0.3 x De<br />
Fig. (c)