25.01.2015 Views

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

Medium Voltage Power Cables Catalogue - AEC Online

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MEDIUM VOLTAGE CABLES<br />

6 / 10 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 6 / 10 (12) kV<br />

Impulse test voltage (peak value) 75 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 21 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Tape<br />

thickness<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

25 5.85 0.3 3.4 0.3 0.076 0.50 42.3 2176 1000<br />

35 6.90 0.3 3.4 0.3 0.076 0.50 44.5 2398 1000<br />

50 8.10 0.3 3.4 0.3 0.076 0.50 47.7 2749 1000<br />

70 9.70 0.3 3.4 0.3 0.076 0.50 51.5 3204 1000<br />

95 11.30 0.3 3.4 0.3 0.076 0.50 55.2 3679 500<br />

120 12.60 0.3 3.4 0.3 0.076 0.50 58.4 4155 500<br />

150 14.10 0.3 3.4 0.3 0.076 0.50 61.8 4635 500<br />

185 15.80 0.3 3.4 0.3 0.076 0.50 65.9 5286 500<br />

240 18.10 0.3 3.4 0.3 0.076 0.50 71.5 6248 500<br />

300 20.50 0.3 3.4 0.3 0.076 0.50 77.2 7260 500<br />

400 23.10 0.3 3.4 0.3 0.076 0.80 84.7 9333 400<br />

Cable Code<br />

A316XH3BBGMRDXXI0MR<br />

A317XH3BBGMRDXXI0MR<br />

A318XH3BBGMRDXXI0MR<br />

A319XH3BBGMRDXXI0MR<br />

A345XH3BBGMRDXXI0MF<br />

A346XH3BBGMRDXXI0MF<br />

A347XH3BBGMRDXXI0MF<br />

A348XH3BBGMRDXXI0MF<br />

A349XH3BBGMRDXXI0MF<br />

A350XH3BBGMRDXXI0MF<br />

A351XH3BBGMRDXXI0MU<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

25 1.2000 1.5386 0.150 1.546 0.202<br />

95<br />

81<br />

103<br />

35 0.8680 1.1131 0.143 0.122 0.224<br />

113<br />

97<br />

124<br />

50 0.6410 0.8221 0.133 0.833 0.249<br />

133<br />

114<br />

147<br />

70 0.4430 0.5684 0.126 0.582 0.282<br />

162<br />

140<br />

183<br />

95 0.3200 0.4110 0.120 0.428 0.316<br />

192<br />

168<br />

221<br />

120 0.2530 0.3253 0.116 0.345 0.343<br />

218<br />

191<br />

253<br />

150 0.2060 0.2653 0.113 0.288 0.374<br />

244<br />

215<br />

287<br />

185 0.1640 0.2118 0.109 0.238 0.409<br />

275<br />

244<br />

328<br />

240 0.1250 0.1624 0.105 0.193 0.456<br />

318<br />

284<br />

385<br />

300 0.1000 0.1311 0.102 0.166 0.505<br />

357<br />

321<br />

439<br />

400 0.0778 0.1036 0.099 0.143 0.559<br />

406<br />

368<br />

508<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)