MEDIUM VOLTAGE CABLES<br />

12 / 20 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 12 / 20 (24) kV<br />

Impulse test voltage (peak value) 125 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 42 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Tape<br />

thickness<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

35 6.90 0.3 5.5 0.3 0.076 0.50 54.7 3337 500<br />

50 8.10 0.3 5.5 0.3 0.076 0.50 57.7 3712 500<br />

70 9.70 0.3 5.5 0.3 0.076 0.50 61.4 4198 500<br />

95 11.30 0.3 5.5 0.3 0.076 0.50 65.2 4750 500<br />

120 12.60 0.3 5.5 0.3 0.076 0.50 68.4 5273 500<br />

150 14.10 0.3 5.5 0.3 0.076 0.50 71.9 5810 500<br />

185 15.80 0.3 5.5 0.3 0.076 0.50 76.2 6558 500<br />

240 18.10 0.3 5.5 0.3 0.076 0.80 82.9 8360 500<br />

300 20.50 0.3 5.5 0.3 0.076 0.80 88.5 9480 400<br />

400 23.10 0.3 5.5 0.3 0.076 0.80 94.9 10958 350<br />

Cable Code<br />

A317XK3BBGMRDXXI0MF<br />

A318XK3BBGMRDXXI0MF<br />

A319XK3BBGMRDXXI0MF<br />

A345XK3BBGMRDXXI0MF<br />

A346XK3BBGMRDXXI0MF<br />

A347XK3BBGMRDXXI0MF<br />

A348XK3BBGMRDXXI0MF<br />

A349XK3BBGMRDXXI0MF<br />

A350XK3BBGMRDXXI0MU<br />

A351XK3BBGMRDXXI0MV<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

35 0.8680 1.1130 0.161 1.125 0.159<br />

113<br />

97<br />

124<br />

50 0.6410 0.8221 0.149 0.836 0.175<br />

133<br />

114<br />

147<br />

70 0.4430 0.5683 0.141 0.586 0.196<br />

162<br />

140<br />

183<br />

95 0.3200 0.4108 0.134 0.432 0.217<br />

192<br />

168<br />

221<br />

120 0.2530 0.3251 0.130 0.350 0.234<br />

218<br />

191<br />

253<br />

150 0.2060 0.2651 0.126 0.293 0.254<br />

244<br />

215<br />

287<br />

185 0.1640 0.2116 0.121 0.244 0.276<br />

275<br />

244<br />

328<br />

240 0.1250 0.1621 0.116 0.199 0.305<br />

318<br />

284<br />

385<br />

300 0.1000 0.1306 0.112 0.172 0.336<br />

357<br />

321<br />

439<br />

400 0.0778 0.1030 0.108 0.149 0.369<br />

406<br />

368<br />

508<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)