MEDIUM VOLTAGE CABLES<br />

8.7 / 15 kV<br />

TECHNICAL DATA<br />

Rated voltage U o / U (U m ) 8.7 / 15 (17.5) kV<br />

Impulse test voltage (peak value) 95 kV<br />

<strong>Power</strong> frequency test voltage for 5 minutes 30.5 kV<br />

Max. conductor operating temperature at Normal conditions 90 °C<br />

Max. conductor operating temperature at Emergency conditions 130 °C<br />

Max. conductor operating temperature at Short circuit conditions 250 °C<br />

Min. bending radius during installation in terms of cable outer diameter 12 Ø<br />

Constructional Data<br />

Nominal<br />

area of<br />

conductor<br />

Conductor<br />

Approx.<br />

conductor<br />

diameter<br />

Insulation Screen Armour Packing<br />

Thickness of insulation layers<br />

C.S XLPE I.S<br />

Min. Nom. Min.<br />

Approx.<br />

metallic<br />

screen tape<br />

thickness<br />

Wire<br />

diameter<br />

Approx.<br />

overall<br />

diameter<br />

Approx.<br />

overall<br />

weight<br />

Standard<br />

cutting<br />

length<br />

± 5 %<br />

mm 2 mm mm mm mm mm mm mm kg / km m<br />

25 5.85 0.3 4.5 0.3 0.076 2.50 50.7 4081 1000<br />

35 6.90 0.3 4.5 0.3 0.076 2.50 53.0 4391 1000<br />

50 8.10 0.3 4.5 0.3 0.076 2.50 56.0 4827 1000<br />

70 9.70 0.3 4.5 0.3 0.076 2.50 59.7 5404 1000<br />

95 11.30 0.3 4.5 0.3 0.076 2.50 63.7 6075 500<br />

120 12.60 0.3 4.5 0.3 0.076 2.50 66.9 6698 500<br />

150 14.10 0.3 4.5 0.3 0.076 3.15 72.3 8258 500<br />

185 15.80 0.3 4.5 0.3 0.076 3.15 76.3 9081 500<br />

240 18.10 0.3 4.5 0.3 0.076 3.15 81.9 10354 400<br />

300 20.50 0.3 4.5 0.3 0.076 3.15 87.7 11684 400<br />

400 23.10 0.3 4.5 0.3 0.076 3.15 93.9 13275 350<br />

Cable Code<br />

A316XJ3BBWMRDXXI0MR<br />

A317XJ3BBWMRDXXI0MR<br />

A318XJ3BBWMRDXXI0MR<br />

A319XJ3BBWMRDXXI0MR<br />

A345XJ3BBWMRDXXI0MF<br />

A346XJ3BBWMRDXXI0MF<br />

A347XJ3BBWMRDXXI0MF<br />

A348XJ3BBWMRDXXI0MF<br />

A349XJ3BBWMRDXXI0MU<br />

A350XJ3BBWMRDXXI0MU<br />

A351XJ3BBWMRDXXI0MV<br />

Electrical Data<br />

Nominal<br />

area<br />

of<br />

conductor<br />

Electrical Characteristics<br />

Max. Conductor<br />

Resistance<br />

Reactance<br />

(60 Hz)<br />

DC at<br />

20 °C<br />

AC at<br />

90 °C<br />

Impedance<br />

(90 °C,<br />

60 Hz)<br />

Capacitance<br />

Buried direct<br />

in the ground<br />

Continuous Current Ratings<br />

In a buried duct<br />

In air<br />

Fig. (a) Fig. (b) Fig. (c)<br />

mm 2 Ω / km Ω / km Ω / km Ω / km μF / km A A A<br />

25 1.2000 1.5386 0.161 1.547 0.166<br />

96<br />

82<br />

105<br />

35 0.8680 1.1130 0.153 1.123 0.183<br />

114<br />

98<br />

126<br />

50 0.6410 0.8221 0.142 0.834 0.202<br />

133<br />

116<br />

150<br />

70 0.4430 0.5684 0.134 0.584 0.228<br />

162<br />

142<br />

185<br />

95 0.3200 0.4109 0.128 0.430 0.253<br />

193<br />

169<br />

224<br />

120 0.2530 0.3252 0.124 0.348 0.273<br />

217<br />

192<br />

256<br />

150 0.2060 0.2652 0.120 0.291 0.297<br />

243<br />

215<br />

289<br />

185 0.1640 0.2117 0.115 0.241 0.324<br />

273<br />

243<br />

329<br />

240 0.1250 0.1622 0.111 0.197 0.360<br />

312<br />

280<br />

384<br />

300 0.1000 0.1308 0.107 0.169 0.397<br />

348<br />

314<br />

434<br />

400 0.0778 0.1032 0.104 0.146 0.438<br />

390<br />

354<br />

495<br />

Fig. (a)<br />

Fig. (b)<br />

0.3 x De<br />

Fig. (c)