<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

2.1.4 Cooling Configuration<br />

Figure 2.1.8: Cooling configuration screen<br />

• Number of Cooling Stages: You can select the number of cooling stages used by the<br />

<strong>Basic</strong> <strong>Rooftop</strong>.<br />

• NONE: The rooftop controller will not perform any cooling actions. Outputs 2<br />

and 3 are inert. Cooling Setpoints section below is completely disabled.<br />

• 1: Only the first stage of cooling is enabled (Output 2). Output 3 is inert. Only<br />

the first stage in the Cooling Setpoints section below is enabled.<br />

• 2: Stages 1 and 2 are enabled (Output 2 and 3). The two first stages in the<br />

Cooling Setpoints section below are enabled. This is the default setting.<br />

• 3*: Stages 1 to 3 are enabled (Output 2). The three first stages in the Cooling<br />

Setpoints section below are enabled.<br />

• 4*: All cooling stages are enabled (Output 2). The Cooling Setpoints section<br />

below is completely enabled.<br />

16<br />

www.prolon.net<br />