<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />
www.prolon.net<br />
• Differential<br />
Units MIN MAX Default<br />
% 8 99 20<br />
• Fourth Stage<br />
• Setpoint<br />
Units MIN MAX Default<br />
% 5 95 90<br />
2.1.4.2 Operation<br />
• Differential<br />
Units MIN MAX Default<br />
% 8 99 19<br />
• Minimum ON Time: Once a stage of cooling is activated, this is the minimum amount of<br />
time it will remain ON, even if cooling is no longer required. It is also the minimum<br />
time required to elapse before the next stage can be engaged.<br />
Units MIN MAX Default<br />
Minutes 0 10 2<br />
• Minimum OFF Time: Once a stage of cooling is deactivated, this is the minimum<br />
amount of time it will remain OFF, even if cooling is required.<br />
Units MIN MAX Default<br />
Minutes 0 10 5<br />
2.1.4.3 Analog Cooling<br />
This function allows for analog cooling when a PTA2 interface is installed on Output 2.<br />
Output 3 is inert. Output 2 pulses with a pulse length proportional to the analog output.<br />
This does not mean that the PTA2 will pulse. For more details on the PTA2 device,<br />
consult the PTA2 Specifications and Installation <strong>Guide</strong>s or the <strong>Rooftop</strong> Hardware <strong>Guide</strong>.<br />
Setpoint:<br />
Proportional:<br />
Units MIN MAX Default<br />
% 5 95 35<br />
Units MIN MAX Default<br />
% 8 95 20<br />