<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

• Differential<br />

Units MIN MAX Default<br />

% 8 99 20<br />

• Fourth Stage<br />

• Setpoint<br />

Units MIN MAX Default<br />

% 5 95 90<br />

2.1.4.2 Operation<br />

• Differential<br />

Units MIN MAX Default<br />

% 8 99 19<br />

• Minimum ON Time: Once a stage of cooling is activated, this is the minimum amount of<br />

time it will remain ON, even if cooling is no longer required. It is also the minimum<br />

time required to elapse before the next stage can be engaged.<br />

Units MIN MAX Default<br />

Minutes 0 10 2<br />

• Minimum OFF Time: Once a stage of cooling is deactivated, this is the minimum<br />

amount of time it will remain OFF, even if cooling is required.<br />

Units MIN MAX Default<br />

Minutes 0 10 5<br />

2.1.4.3 Analog Cooling<br />

This function allows for analog cooling when a PTA2 interface is installed on Output 2.<br />

Output 3 is inert. Output 2 pulses with a pulse length proportional to the analog output.<br />

This does not mean that the PTA2 will pulse. For more details on the PTA2 device,<br />

consult the PTA2 Specifications and Installation <strong>Guide</strong>s or the <strong>Rooftop</strong> Hardware <strong>Guide</strong>.<br />

Setpoint:<br />

Proportional:<br />

Units MIN MAX Default<br />

% 5 95 35<br />

Units MIN MAX Default<br />

% 8 95 20<br />