<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

• Weighted Average (heating only): This is the same as “Weighted Average”,<br />

except only zones with a heating demand are included in the calculation.<br />

• Weighted Average (cooling only): This is the same as “Weighted Average”,<br />

except only zones with a cooling demand are included in the calculation.<br />

• Occupancy: If there is at least one slave found in this calculation that is<br />

occupied (or overridden to be occupied), this math function will return 100%,<br />

otherwise it will be 0%.<br />

• Override: If there is at least one slave found in this calculation that is<br />

overridden from unoccupied to occupied mode, this math function will return<br />

100%, otherwise it will be 0%<br />

• Global: When this is selected, ALL slaves on the system are included in the<br />

calculation. The global weight of each slave device will be used in the calculations.<br />

• Group Code: When this is selected, ONLY the slaves belonging to this group are<br />

included in the calculation. There are 250 groups available, numbered 1 through 250.<br />

The group weight of each slave controller belonging to that group will be used in the<br />

calculation. When Group Codes are not being used, they are automatically set to<br />

zero.<br />

Units MIN MAX Default<br />

N/A 1 250 0 (Not used)<br />

• Poll Rate: The rate at which this master will update all the slaves on the system and<br />

receive new information from them. Increase this value to alleviate network traffic.<br />

Units MIN MAX Default<br />

Seconds 1 250 3<br />

During a Master/Slave data transaction, the exchanged data is as follows:<br />

Master Slave:<br />

• Supply temperature<br />

• Outside temperature<br />

• Occupancy status of the master<br />

• Morning warm up command<br />

• Override of Outputs 3, 4 or 5 based on the outside temperature<br />

• Damper Override<br />

Slaves Master<br />

• Demand<br />

• Group codes and weights<br />

• Global weight<br />

• Override status<br />

• Supply temperature, if this slave is the source of the system’s supply<br />

temperature (see below)<br />

36<br />

www.prolon.net<br />