• Weighted Average (heating only): This is the same as “Weighted Average”,<br />
except only zones with a heating demand are included in the calculation.<br />
• Weighted Average (cooling only): This is the same as “Weighted Average”,<br />
except only zones with a cooling demand are included in the calculation.<br />
• Occupancy: If there is at least one slave found in this calculation that is<br />
occupied (or overridden to be occupied), this math function will return 100%,<br />
otherwise it will be 0%.<br />
• Override: If there is at least one slave found in this calculation that is<br />
overridden from unoccupied to occupied mode, this math function will return<br />
100%, otherwise it will be 0%<br />
• Global: When this is selected, ALL slaves on the system are included in the<br />
calculation. The global weight of each slave device will be used in the calculations.<br />
• Group Code: When this is selected, ONLY the slaves belonging to this group are<br />
included in the calculation. There are 250 groups available, numbered 1 through 250.<br />
The group weight of each slave controller belonging to that group will be used in the<br />
calculation. When Group Codes are not being used, they are automatically set to<br />
zero.<br />
Units MIN MAX Default<br />
N/A 1 250 0 (Not used)<br />
• Poll Rate: The rate at which this master will update all the slaves on the system and<br />
receive new information from them. Increase this value to alleviate network traffic.<br />
Units MIN MAX Default<br />
Seconds 1 250 3<br />
During a Master/Slave data transaction, the exchanged data is as follows:<br />
Master Slave:<br />
• Supply temperature<br />
• Outside temperature<br />
• Occupancy status of the master<br />
• Morning warm up command<br />
• Override of Outputs 3, 4 or 5 based on the outside temperature<br />
• Damper Override<br />
Slaves Master<br />
• Demand<br />
• Group codes and weights<br />
• Global weight<br />
• Override status<br />
• Supply temperature, if this slave is the source of the system’s supply<br />
temperature (see below)<br />
36<br />
www.prolon.net<br />