<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

2.1.5 Heating Configuration<br />

Figure 2.1.9: Heating configuration screen<br />

• Heating Demand Source: All heating functions are regulated by the same demand<br />

source. This source is one of the predefined math functions (see Math Functions<br />

p.35). You can select “Math 1” through “Math 5”.<br />

2.1.5.1 Digital Output 4<br />

• Function: Select the function of Output 4.<br />

• OFF: Output 4 is always OFF.<br />

• Preheat Permission: Output 4 is used for preheating permission. Permission<br />

is granted when the fan in ON and when there is no active cooling for a<br />

specified time period (see Delay between Heating and Cooling, page 27), and<br />

when the outside air limit is met (See p.24). This is the default setting.<br />