<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />
www.prolon.net<br />
2.1.5 Heating Configuration<br />
Figure 2.1.9: Heating configuration screen<br />
• Heating Demand Source: All heating functions are regulated by the same demand<br />
source. This source is one of the predefined math functions (see Math Functions<br />
p.35). You can select “Math 1” through “Math 5”.<br />
2.1.5.1 Digital Output 4<br />
• Function: Select the function of Output 4.<br />
• OFF: Output 4 is always OFF.<br />
• Preheat Permission: Output 4 is used for preheating permission. Permission<br />
is granted when the fan in ON and when there is no active cooling for a<br />
specified time period (see Delay between Heating and Cooling, page 27), and<br />
when the outside air limit is met (See p.24). This is the default setting.<br />